Appendix 3
DC12V
Line and Transmission Distance
Table
When the size of the line is certain,
DC12V
voltage loss rate is less
than 10%, the recommended maximum transmission distance. (For the
exchange of electricity supply equipment, its maximum allowable
voltage loss of 10%). For example: one equipment, the rated power
80VA, installed 35 feet(10m) distance from the transformer, the need
size of the smallest diameter is 0.8000mm.
distance(m)
power(VA)
Line (mm)
0.8000
1.000
1.250
2.000
10
283(86)
451(137)
716(218)
1811(551)
20
141(42)
225(68)
358(109)
905(275)
30
94(28)
150(45)
238(72)
603(183)
40
70(21)
112(34)
179(54)
452(137)
50
56(17)
90(27)
143(43)
362(110)
60
47(14)
75(22)
119(36)
301(91)
70
40(12)
64(19)
102(31)
258(78)
80
35(10)
56(17)
89(27)
226(68)
90
31(9)
50(15)
79(24)
201(61)
100
28(8)
45(13)
71(21)
181(55)
110
25(7)
41(12)
65(19)
164(49)
120
23(7)
37(11)
59(17)
150(45)
130
21(6)
34(10)
55(16)
139(42)
140
20(6)
32(9)
51(15)
129(39)
150
18(5)
30(9)
47(14)
120(36)
160
17(5)
28(8)
44(13)
113(34)
170
16(4)
26(7)
42(12)
106(32)
180
15(4)
25(7)
39(11)
100(30)