5.

 

Control mode 

Superheat control

 

( DIP SW1 : OFF, DIP SW4 : OFF ) 

 

In most cases, it would aim to control superheat. 
 

Definition 

Description 

Definition 

Description 

COMP 

Compressor 

Evaporator 

Evaporator 

EEV 

Electronic expansion valve 

EVC10 

Electronic expansion valve 
controller 

T-sens 

Temp. sensor of evaporator 
outlet 

Run 

Run / Stop switch  

P-sens 

Suction pressure sensor of 
compressor  

 

 

Application parameter 

Function 

CODE 

Min. 

Max. 

Default 

Superheat set point  

SH 

0.5 

30 

6.0 K 

Start open ratio 

BIR 

100 

0 % 

Start open ratio duration time 

SDT 

60 

0 Sec. 

P: Proportional gain  

DFR 

0.1 

50.0 

3.0 % 

I:Integral time 

I RT 

999 

120 Sec. 

D:Derivative time 

DRT 

999 

30 Sec. 

 

Temperature control (Hot gas bypass)

 

( DIP SW1 : OFF, DIP SW4 : ON ) 

 

It will be used when controlling temperature of control object accurately by 
adjusting by-pass amount of hot gas. 

Definition 

Description 

Definition 

Description 

COMP 

Compressor 

Evaporator 

Evaporator 

EEV 

Electronic expansion valve 

EVC10 

Electronic expansion valve 
controller 

T-sens 

Temp. sensor of 
evaporator outlet 

Run 

Run / Stop switch  

TEV 

Thermostatic expansion 
valve 

 

 

Application parameter 

Function 

CODE 

Min. 

Max. 

Default 

Set point for control target** 

SH 

-100 

+100 

6.0 ℃ 

Start open ratio 

BIR 

100 

0 % 

Start open ratio duration time 

SDT 

60 

0 Sec. 

P: Proportional gain  

DFR 

0.1 

50.0 

3.0 % 

I:Integral time 

I RT 

999 

120 Sec. 

D:Derivative time 

DRT 

999 

30 Sec. 

**

 

Parameter will be changed and applied from superheat set point to temperature set point of 

control object. 

Drive function

 

( DIP SW1 : ON, DIP SW4 : ON ) 

 

※ To use drive function of expansion valve using external reference signal, change operation 
mode to drive mode. At this time, it will be operated when Run should be ON. Expansion valve 
will be closed immediately when turning OFF Run. 

Manual control mode

 

( DIP SW1 : ON, DIP SW4 : OFF ) 

 

- Users can maintain valve open ration arbitrarily. Input it using +/- button 
after setup operation mode to manual mode.   
At this time all LED on the left side will be flickering.   
In case of manual control mode, Run should be ON. Expansion valve will be closed immediately 
when turning OFF Run 

 

 

State Message

 

CODE 

Description 

STP 

Operation stop   

CAL 

Expansion valve initialization   

PDN 

Pump down operation   

 

 

 

Summary of Contents for EVC10B Series

Page 1: ...sed to control machineries Medical equipment vehicle train airplane combustion apparatus entertainment processing and transportation equipment elevator and various safety device etc enabling to effect...

Page 2: ...40 120 Protection level IP65 Accuracy 1 0 F S Stability 0 5 Longterm Stability Connector Type 7 16 UNF FEMALE Wiring Black com Green out Red 5v 2 Installation Dimensions It can be installed with rail...

Page 3: ...nsion valve First of all EVC10B needs to setup EEV mode to fit features of electronic expansion valve If EEV mode does not meet operation features of electronic expansion valve there can be malfunctio...

Page 4: ...d save Display mode DIS parameter of parameter 2 group value will be changed Superheat Pressure of evaporator outlet Currentopenration ofEEV Temperature of evaporator outlet 4 Parameter Parameter chan...

Page 5: ...g protection alarm is occurred caused by temperature of evaporator is getting low expansionvalveisfullyclosed 8Pumpdownfunction If input pumpdown delay time of 0 to 180 sec auxiliary relay RL1 outputs...

Page 6: ...re shipment Setting 2 group table Menu 3 3 PR Users should input parameter which is suitable for characteristic of expansion valve In case of difference it may be caused by malfunction or valve and sy...

Page 7: ...icexpansionvalve controller T sens Temp sensor of evaporatoroutlet Run Run Stopswitch TEV Thermostaticexpansion valve Application parameter Function CODE Min Max Default Setpointforcontroltarget SH 10...

Page 8: ...sent pressure remains lower than set value of LOP duringLDP Lowlimitpressurealarmdelaytime Itwillbecausedbylackof refrigerant Itbecomesaclearconditionifpresentpressureismorethan setvalueofLPF LP 2 Fli...

Reviews: