-4-
EVC10B R20140821
3.
User interface
: Lamp & Operation button
Definition
Description
LED
Super Heat
When displaying superheat
Pressure
When displaying pressure
Open %
When displaying valve open ratio
Temp
When displaying temperature
℃, bar
Display the unit of temp. / pressure
Lighting when warning
(Flickering when manual return alarm
occurs)
Flickering at manual open ratio control
POWER
Lighting at power up
TX, RX
Flickering in communication
Button
Parameter change mode
Increase or upward
Decrease or downward
Select and save
Display mode (DIS) parameter of parameter
2 group value will be changed.
Superheat --- (▲▼)--- Pressure of evaporator
outlet ---(▲▼)--- Current open ration of EEV ---
(▲▼)--- Temperature of evaporator outlet
4.
Parameter
: Parameter change
● Press PRG button for 3 seconds to change setting parameters.
※ password is not correct, state check is only available, but can’t change parameters.)
● Movement to next menu and storage of set value during parameter setup are performed by SEL button.
● Set value will be flickering in every 0.5 seconds and change set value using ▲ or ▼ key.
● Present flow value will be displayed if pressing SEL button for 3 seconds after finished setup.
● If there is no input for 30 minutes during setup, it will be returned to operation mode.