Setting 2 group table

 (Menu 2 = 

2.PR

※1 Password 

It is necessary to input password to change or initialize parameters and default 
value is “5”. Be sure to take notes not to forget or loss it after changing 
password. 

※2 Setup max. and min. range of pressure sensor 

Setup max. and min. range of pressure sensor. Pressure sensor is a ratiometric 
type of 0.5~4.5V. Default value before shipment is 1~15bar. 

※3 Setup pressure sensor offset correction 

Users can input offset correction value for pressure sensor, temperature sensor 
and input error. It was set 0.0 as a default value. 

※4 Jerk control ratio 

Limit value of motor speed variation (Jerk Control) 

※5 Expansion valve compulsory open ratio 

If users want to temporarily control expansion valve by designated open ratio 
while controlling normally. Default value before shipment is OFF. 

※6 Sensor filter input time 

Only expert can setup this parameter. If sensor input is excessively unstable, 
increase filter value and make it stable. 

※7 EEV compulsory open ratio 

It can be used to temporarily control electronic expansion valve with designated 
open ratio when controlling normally. 
Default value is set as not in use.

 

※8 

Way to change of display mode

 

Press up / downward button to change parameters  
(DIS parameter will be changed)  
Parameter number will be displayed for one second before parameter is 
displayed. 
* It is possible to change with direct input when displaying superheat set point.

 

※9 Initialization 

If password is entered, parameters will be initialized as an default value before 
shipment. 

Setting 2 group table

 (Menu 3 = 

3.PR

※ Users should input parameter which is suitable for characteristic of expansion valve.  In case of difference,  

it may be caused by malfunction or valve and system will be damaged. 

 

 

Address 

Description 

Code 

Unit 

Step 

Min. 

Max. 

Default 

Custom 

4 0061 

Password 

PCD 

999 

 

4 0062 

Type of refrigerant 

RFY 

22

(0)= R22 

134

(1)= R134A 

404

(2)= R404A 

407

(3)= R407C 

410

(4)= R410A 

717(

5)= R717 

23

(6)= R23 

507

(7)= R507C 

22

(0) 

 

4 0063 

Pressure sensor Max. range (at 4.5V) 

PSH 

bar 

-1 

99 

15 

 

4 0064 

Pressure sensor Min. range (at 0.5V) 

PSL 

bar 

-1 

99 

-1 

 

4 0065 

Pressure sensor offset correction 

PCR 

0.1 

-9.9 

9.9 

0.0 

 

4 0066 

Temp. sensor offset correction 

TCR 

0.1 

-19.9 

19.9 

0.0 

 

4 0069 

Jerk control ratio ※4 

JEY 

 

0.1 

0.1 

100.0 

100.0 

 

4 0070 

Expansion valve open ratio upper limit 

OPH 

100 

100 

 

4 0071 

Expansion valve open ratio lower limit 

OPL 

100 

 

4 0072 

EEV compulsory open ratio 

O 11 

0.1 

0.1 

10.0 

1.0 

 

4 0073 

Sensor input filter time   

UCR 

0.1 

0.0 

100.0 

OFF

(-1) 

 

4 0076 

Display mode 

D I S 

0= 1~4 Rotation 
1= Superheat 
2= Evaporator outlet pressure 

3= Expansion valve open ratio 
4= Evaporator outlet temperature 
5= Saturation temperature 

 

4 0077 

Run/Stop method 

RMT 

0=  Always run 

1=  Digital input(RUN) 

2=  Communication Run 

 

4 0078 

Communication ID setup 

ID 

254 

 

4 0079 

Communication speed (BPS) setup 

BDR 

48

(0)= 4800 

96

(1)= 9600 

192

(2)= 19200 

384

(3)= 38400 

96 

 

 

Initialization 

RST 

999 

 

Address 

Description 

Code 

Unit 

Step 

Min. 

Max. 

Default 

Custom 

4 0042 

Expansion valve excitation type 

EVD 

1-2

 = 1-2

 phase excitation

 

2

 = 2

 phase excitation

 

 

4 0043 

Expansion valve TOTAL PULSE 

EVP 

PULSE 

100 

999 

200 

 

4 0044 

Expansion valve OPEN PULSE 

EVO 

PULSE 

999 

100 

 

4 0045 

Expansion valve DRIVE SPEED (PPS) 

EVS 

10

(0)=  10PPS 

20

(1)= 20PPS 

30

(2)= 30PPS 

 

50

(3)= 50PPS 

80

(4)= 80PPS 

100

(5)= 100PPS 

200

(6)= 200PPS 

250

(7)= 250PPS 

500

(8)= 500PPS 

200 

 

Summary of Contents for EVC10B Series

Page 1: ...sed to control machineries Medical equipment vehicle train airplane combustion apparatus entertainment processing and transportation equipment elevator and various safety device etc enabling to effect...

Page 2: ...40 120 Protection level IP65 Accuracy 1 0 F S Stability 0 5 Longterm Stability Connector Type 7 16 UNF FEMALE Wiring Black com Green out Red 5v 2 Installation Dimensions It can be installed with rail...

Page 3: ...nsion valve First of all EVC10B needs to setup EEV mode to fit features of electronic expansion valve If EEV mode does not meet operation features of electronic expansion valve there can be malfunctio...

Page 4: ...d save Display mode DIS parameter of parameter 2 group value will be changed Superheat Pressure of evaporator outlet Currentopenration ofEEV Temperature of evaporator outlet 4 Parameter Parameter chan...

Page 5: ...g protection alarm is occurred caused by temperature of evaporator is getting low expansionvalveisfullyclosed 8Pumpdownfunction If input pumpdown delay time of 0 to 180 sec auxiliary relay RL1 outputs...

Page 6: ...re shipment Setting 2 group table Menu 3 3 PR Users should input parameter which is suitable for characteristic of expansion valve In case of difference it may be caused by malfunction or valve and sy...

Page 7: ...icexpansionvalve controller T sens Temp sensor of evaporatoroutlet Run Run Stopswitch TEV Thermostaticexpansion valve Application parameter Function CODE Min Max Default Setpointforcontroltarget SH 10...

Page 8: ...sent pressure remains lower than set value of LOP duringLDP Lowlimitpressurealarmdelaytime Itwillbecausedbylackof refrigerant Itbecomesaclearconditionifpresentpressureismorethan setvalueofLPF LP 2 Fli...

Reviews: