DOTECH EVC10B Series User Manual Download Page 3

-3-

 

EVC10B R20140821 

: Details of terminal 

No. 

Definition 

Description  

J1.1 

AC / DC 

24V 

+24V 

Power input  AC24V or DC24V+ 

J1.2 
J1.3 

-24V 

Power input  AC24V or DC24V- 

J1.4 

J2.1 

RUN 

SIG 

Run / Stop signal input 

J2.2 

GND 

Signal common 

J3.1 

RS485 

TRX+ 

RS485 comm. TRX+(A) 

J3.2 

TRX- 

RS485 comm. TRX-(B) 

J4.1 

AUX-RLY 

N.O 

Auxiliary relay - Normal Open contact 

J4.2 

COM 

Auxiliary relay -  common 

J4.2 

N.C 

Auxiliary relay - Normal Close contact 

 

No.

Definition

Description  

J5.1

P-SENS

+5V

Power output for pressure 5V) 

J5.2

S1

Pressure sensor signal input 

J5.3

GND

Pressure sensor power signal common 

J6.1

T-SENS

S2

Temperature sensor 

J6.2

GND

Temperature sensor common 

J7.1

EEV 

MOTOR

A

EEV phase 1(A) 

J7.2

B

EEV phase 1(B) 

J7.3

A#

EEV phase 2(A#) 

J7.4

B#

EEV phase 2(B#) 

J7.5

COM

EEV common 

J7.6

COM

EEV common 

 

1) Operation start and stop instruction 

If SIG signal is short circuited (on), it will start to run. In case of opening (off), 
operation will be stopped and expansion valve is closed immediately. 
 

2) Utilization of auxiliary rely 

Auxiliary  relay  can  be  used  for  alarm  or  compressor  ON/OFF  or  liquid  valve 
ON/OFF In case of Pd= Off, use it as an alarm purpose. 
If users enter pump down time (1~180 sec), it will be used for ON/OFF signal of 
compressor. 

 

3) Selection of electronic expansion valve 

First  of  all,  EVC10B  needs  to  setup  EEV  mode  to  fit  features  of  electronic 

expansion valve. If EEV mode does not meet operation features of electronic 
expansion valve, there can be malfunction. Please check it without fail. Operate 
only number 2 and 3 of DIP SWITCH (DSW). After changing of setting, push 
RES button on the right of product and restart. Users may input power 
again. 

DIP 

SW 2 

DIP 

SW 3 

MAKER & MODE 

SPEC. 

OFF 

OFF 

SANHUA-DPF(Q), DPF(R) 
JAHWA-SEV, JHEV 
FUJIKOKI-CAM 
SAGINOMIYA-
UKV,SKV,VKV,PKV,AKV 

1-2 PH excitation type 
500 PULSE 
30 PPS  

OFF 

ON 

SANHUA-DPF(O) 
FUJIKOKI-EDM 
GREEN-GV321,521,641 

2 PH excitation type  
2000 PULSE 
100 PPS  

ON 

ON 

Direct input by user 

Setup at 
parameter 3 group 

※ In case of DPF(O)-8.0, change set value after altering into user mode. 

(DIP SW 2,3 = ON) 

Function 

CODE 

Min.

Max. 

Default

Changed 

Value 

Expansion valve 
excitation type 

EVD 

Expansion valve TOTAL 
PULSE 

EVP 

100

999 

200 

250 

Expansion valve OPEN 
PULSE 

EVO 

999 

100 

100 

Expansion valve DRIVE 
SPEED (PPS) 

EVS 

18 

 

4) Selection of control mode 

Operation 

mode  

DIP SW 

Description 

Automatic
mode  

OFF

OFF

- Superheat control 
- Possible to operate valve via  

RS485 comm. 

Drive 

ON 

ON 

- Operate valve receiving external  

signal from J5 port 

Manual 
operation

ON 

OFF

- Operate valve using UP/DOWN button. 
- Possible to operate valve via  

RS485 comm. 

Temp. 
control 

OFF

ON 

- Precise temp. control by controlling hot gas 

bypass 

※ It does not detect alarm at drive and manual operation mode.

 

 

Summary of Contents for EVC10B Series

Page 1: ...sed to control machineries Medical equipment vehicle train airplane combustion apparatus entertainment processing and transportation equipment elevator and various safety device etc enabling to effect...

Page 2: ...40 120 Protection level IP65 Accuracy 1 0 F S Stability 0 5 Longterm Stability Connector Type 7 16 UNF FEMALE Wiring Black com Green out Red 5v 2 Installation Dimensions It can be installed with rail...

Page 3: ...nsion valve First of all EVC10B needs to setup EEV mode to fit features of electronic expansion valve If EEV mode does not meet operation features of electronic expansion valve there can be malfunctio...

Page 4: ...d save Display mode DIS parameter of parameter 2 group value will be changed Superheat Pressure of evaporator outlet Currentopenration ofEEV Temperature of evaporator outlet 4 Parameter Parameter chan...

Page 5: ...g protection alarm is occurred caused by temperature of evaporator is getting low expansionvalveisfullyclosed 8Pumpdownfunction If input pumpdown delay time of 0 to 180 sec auxiliary relay RL1 outputs...

Page 6: ...re shipment Setting 2 group table Menu 3 3 PR Users should input parameter which is suitable for characteristic of expansion valve In case of difference it may be caused by malfunction or valve and sy...

Page 7: ...icexpansionvalve controller T sens Temp sensor of evaporatoroutlet Run Run Stopswitch TEV Thermostaticexpansion valve Application parameter Function CODE Min Max Default Setpointforcontroltarget SH 10...

Page 8: ...sent pressure remains lower than set value of LOP duringLDP Lowlimitpressurealarmdelaytime Itwillbecausedbylackof refrigerant Itbecomesaclearconditionifpresentpressureismorethan setvalueofLPF LP 2 Fli...

Reviews: