
-5-
EVC10B R20140821
: Setting 1 group table
(Menu 1 =
1.PR
)
※1 Start open ration and start open ratio duration time
If Run switch is turned on, valve will be opened by start open ratio. After that maintain it during
start open ratio duration time and start to control. (Input optimum value as a start open ratio)
※2 Setup of proportional gain
In the majority of cases, use the result of auto tuning. Extra changes are unnecessary.
Proportional gain makes a decision on control input of valve open ratio
according to superheat change. If proportional gain is 3.0%, control input of
valve open ratio is 3.0% per 1.0K of superheat.
If change of valve open ratio is fickle, decrease proportional gain.
If change of valve open ratio is slow, increase proportional gain more.
Open ratio of valve [%] = Start open ratio + (Proportional gain X Tolerance)
※3 Setup of integral time and derivative time
In the majority of cases, use the result of auto tuning. Extra changes are unnecessary.
Integral time: Input time which is applied to control for accumulated volume of tolerance.
Derivative time: It is for controlling momentary reacting volume for tolerance
If vibration time is longer than integral time,
1. Integral time increases 1.5 times of vibration time.
2. Wait until system is stable.
3. If vibration is lasting, decrease integral time 30%.
4. Wait until system is stable
5. Repeat 3 and 4 until vibration is removed.
If vibration time is shorter than integral time
1. Decrease proportional gain 30%.
2. Wait until system is stable
3. Repeat 1 and 2 until vibration is removed
※4 Detect low superheat alarm
This alarm is caused by superheat is low. Once superheat begins to low, expansion valve start
to close more. If low superheat alarm is occurred, expansion valve is fully closed.
※5 Maximum operating pressure alarm mode
Once maximum operating pressure alarm is occurred, expansion valve is fully closed.
※6 Detect high superheat alarm
This alarm is caused by superheat is high. Once superheat begins to high, expansion valve
start to open more. If high superheat alarm is occurred, expansion valve is fully closed.
※7 Detect freezing protection alarm
If freezing protection alarm is occurred caused by temperature of evaporator is getting low,
expansion valve is fully closed
※8 Pumpdown function
If input pumpdown delay time of 0 to 180 sec, auxiliary relay (RL1) outputs it
as compressor control purpose.
Run switch turns on, RL1 start to run
Run switch turns off, RL1 will be turned off. (Less than pumpdown finish pressure)
※9 Detect low limit pressure alarm
If pressure is dropping up to less than
LOP
for more than
LPD
, low limit pressure alarm will
be occurred and expansion valve is fully closed.
Address
Description
Code
Unit
Step
Min.
Max.
Default
Custom
4 0001
Superheat set-point
SH
K
0.1
0.5
30
6.0
4 0003
Start open ratio
BIR
%
1
0
100
0
4 0004
Start open ration duration time
SDT
Sec.
1
0
300
0
4 0005
P: Proportional gain
DFR
%
0.1
0.1
99.9
3.0
4 0006
I:Integral time
I RT
Sec.
1
0
999
120
4 0007
D:Derivative time
DRT
Sec.
1
0
999
30
4 0008
Low superheat alarm mode
LS
0=No use
1=automatic return
2= manual return
1
4 0009
Detect low superheat alarm
LSH
K
0.1
0.5
30.0
0.5
4 0010
Low superheat alarm delay time
LSD
Sec.
1
1
300
15
4 0011
Clear low superheat alarm
LSF
K
0.1
1.0
30.5
3.0
4 0012
Maximum operating pressure alarm mode (MOP)
MP
0=No use
1=automatic return
2= manual return
1
4 0013
MOP
alarm detection pressure
MOP
bar
0.1
-1
50
9.0
4 0014
MOP
alarm detection delay time
MPD
Min.
1
1
15
1
4 0015
Clear MOP alarm
MPF
bar
0.1
-1
50
8.0
4 0016
High superheat alarm mode
HS
0=No use
1=automatic return
2= manual return
0
4 0017
Detect high superheat alarm
HSH
K
1
10
40
30
4 0018
High superheat alarm delay time
HSD
Sec.
1
1
600
3
4 0019
Clear high superheat alarm
HSF
K
0.1
7
37
27
4 0021
Freeze prevention alarm mode
FR
0=No use
1=automatic return
2= manual return
0
4 0022
Detect freeze prevention alarm
FRE
℃
1
-40
40
0
4 0023
Freezing protection alarm delay time
FRD
Sec.
1
5
200
30
4 0024
Clear freeze prevention alarm
FRF
℃
1
-37
43
3
4 0025
Select pumpdown function and delay time
PD
Sec.
1
0
180
OFF
(-1)
4 0026
Pressure set-point for stopping pumpdown
PDP
bar
0.1
-0.5
18.0
0.5
4 0027
Pressure low limit alarm mode
LP
0=No use
1=automatic return
2= manual return
0
4 0028
Detect low limit pressure alarm
LOP
bar
0.1
-0.8
17.7
0.0
4 0029
Low limit pressure alarm delay time
LPD
Sec.
1
5
200
5
4 0030
Clear low limit pressure alarm
LPF
bar
0.1
-0.5
18.0
0.3