SafeRoute® System

2019-03

WN 059722 45532

dormakaba

About this document

System manual

About this document

1.1  Contents and purpose 

This document contains the information and 
instructions for the installation and operation of 
a SafeRoute® system on an emergency exit door 
unit according to EltVTR (12/1997 version) and DIN 
EN 13637:2015. The functional scope information 
refers to a SafeRoute® system with the Standard 
license.

1.2  Target group

This document is intended for assembling technicians 
and specialists authorized by dormakaba for the 
installation, operation, maintenance and testing of a 
SafeRoute® system.

1.3  Other applicable documents:

The following documents belong to the unit’s 
complete documentation and must be observed:
•  The installed individual components’ assembly 

instructions and documents  

•  The operation manual
•  The inspection log for the door unit on which the 

SafeRoute® system was installed

•  The TMS Soft® handbook
•  The approved components’ declaration of 

conformity

1.4  Documents storage 

This document and the other applicable documents 
must be handed over to the facility operator after 
commissioning. The facility operator must keep 
the documents for the entire service life and make 
them accessible to the persons responsible for the 
inspection and maintenance of the emergency exit 
door unit.

1.5  Abbreviations

Abbreviation

Definition

SCU-xx

SafeRoute® Control Unit - Control 
unit of a SafeRoute® system in three 
versions:
•  SCU-UP = Flush mounting
•  SCU-TL = in the door terminal 

STL-G

•  SCU-DR = DIN rail mounting

SLI

License card

SLI-A

Application

STL-G

Door terminal with emergency 
button SCU-TL and key switch ST

STV xxx

Electrical door lock

ST

Key switch

1.6  Symbols used

1.6.1  Hazard categories

WARNING

This signal word indicates a situation of 
potential risk, which could lead to death or 
serious injury if not averted.

1.6.2  More symbols

TIPS AND RECOMMENDATIONS

This signal word indicates useful information 
for efficient and trouble-free operation.

Summary of Contents for SafeRoute

Page 1: ... Requirements for mounting a SafeRoute system 5 4 1 1 Door unit 5 4 1 2 Requirements for fire and smoke protection doors 5 4 2 Mounting the components 5 4 2 1 DCW bus addressing door entry system 5 5 Commissioning 5 5 1 Put the SafeRoute system into operation 5 5 1 1 SCU UP and SCU TL as SafeRoute Control Unit 5 5 1 1 1 Configure an SCU UP SCU TL 5 5 1 2 SCU DR as SafeRoute Control Unit from Basic...

Page 2: ...afeRoute system was installed The TMS Soft handbook The approved components declaration of conformity 1 4 Documents storage This document and the other applicable documents must be handed over to the facility operator after commissioning The facility operator must keep the documents for the entire service life and make them accessible to the persons responsible for the inspection and maintenance o...

Page 3: ...sts of various components depending on the requirements 3 1 Parts included Mini Basic or Standard license card Battery for the clock function from license standard System manual Operation manual Inspection logbook 3 2 Technical information Systems according to EltVTR must be operated with 24 V 10 to maintain the retention force for locking devices Systems outside the scope of the EltVTR can be ope...

Page 4: ... can be connected or switched The input and output functions can be parameterized with TMS Soft from the Basic license 3 4 3 RS232 interface at the SCU available from Basic license The SCU with the inserted license card can be connected to TMS Soft PC computer via the RS232 interface The connection can also be made via an LON or LAN network adapter 3 5 Functional scope The functions of a SafeRoute...

Page 5: ...ddress Similar DCW components must have different DCW bus addresses The setting is made via the DCW DIP switches on the components 5 Commissioning 5 1 Put the SafeRoute system into operation Depending on the SafeRoute Control Unit used SCU UP SCU TL or SCU DR from Basic license the procedure and status displays differ 5 1 1 SCU UP and SCU TL as SafeRoute Control Unit The status display is indicate...

Page 6: ...cense In 1 4 off no defective license card In 4 on SLI Basic In 3 on SLI Standard The illuminated ring on the emergency button flashes briefly and changes to the rainbow view 2 Press and hold the S4 service button on the SCU DR for 12 s After 12 s the illuminated ring on the emergency button lights up blue The BTR LED flashes green The connected components are detected and displayed on the illumin...

Page 7: ...signed to any SCU Green SCU emergency button available The indicator flashes green 2 5 Hz if the emergency button is not yet configured Yellow Malfunction STV SCU is missing defective The illuminated ring changes to Initialization view 3 ST DCW 1 I O DCW 1 ST DCW 2 I O DCW 2 ST DCW 3 I O DCW 3 ST DCW 4 I O DCW 4 Blue ST DCW address X available Magenta I O DCW available Yellow Malfunction STV SCU i...

Page 8: ...intact and sealed 2 Turn and hold the key switch to the right The alarm is acknowledged The door remains unlocked Tampering message The STV is locked Tamper alarm has been triggered all door locks on the door are locked 1 Make sure all housings and covers are intact and sealed 2 Turn and hold the key switch to the right The alarm is acknowledged The door unlocks 3 Turn the key switch to the left T...

Page 9: ...button error 1 Push and hold the key to the right on the key switch 2 Press the emergency button for 1 s and then release 3 Push the key over the middle to the left and bring it back to the middle position 4 Remove the key The electric locking device is active If the error occurs again replace the device When locked When permanent open The connection via DCW bus to a standard DCW node is interrupt...

Page 10: ...nterrupted e g due to a loose connection 1 Check the line to STV address 1 2 Acknowledge the error after removal 3 Press the key switch to the right and then to the left The STVxxx locks Maintenance is required The maintenance interval has been exceeded 1 Conduct maintenance or order it according to specifications 2 Reset the maintenance alarm To do this press the key switch to the left for 15 sec...

Page 11: ...the component The component is incorporated in the system 8 2 Remove non safety related DCW components completely 1 Disconnect the wiring to the component 2 Remove the component 3 Delete the component from the system To do this update the internal DCW table see chap 8 4 The component is completely removed from the system 8 3 Replace remove safety related DCW components 1 Use TMS Soft to read the c...

Page 12: ... for smartphone tablet Apple iOS Appstore or Google Android Playstore 10 Disassembly recycling and disposal Disassembly is carried out in the reverse order of mounting and must be carried out by qualified personnel The product must be disposed of in an environmentally friendly manner Electro technical parts and batteries must not be disposed of as domestic waste Dispose of electrotechnical parts a...

Page 13: ... emergency button Direct connection of motor locks SVP 2xxx DCW M SVP 22xx DCW Vis Aud display Status Warning Initialization display on the illuminated ring Adjusting the brightness Adjusting the flashing frequencies Pre alarm main alarm after temporary unlocking and long term unlocking Maintenance alarm Acoustic confirmation when activating long term or permanent unlocking Alarm duration limit Al...

Page 14: ...14 SafeRoute System 2019 03 WN 059722 45532 dormakaba Maintenance System manual ...

Page 15: ...15 SafeRoute System 2019 03 WN 059722 45532 dormakaba System manual Maintenance ...

Page 16: ...www dormakaba com Translation of the original document subject to change without notice dormakaba Deutschland GmbH DORMA Platz 1 58256 Ennepetal Germany T 49 2333 793 0 F 49 2333 793 4950 ...

Reviews: