12-2020
dormakaba Canada Inc. RAC5 XT Installation Guide – PK3737 | 23
Figure 14 – Strike Wiring (Fail Safe)
Fire Alarm
Bypass Wire
(See Note)
+12V Supply
For Locking Device
Strike
Black
Wires
Connector
Red Wire
Black Wire
Note:
To automatically unlock the door in case of fire, remove the Fire Alarm
Bypass wire and connect J18 to the Fire Alarm panel as per Fire
Alarm Panel Wiring diagram (see Annex B, Figure 10).
In this case the Electric Strike MUST be powered from the RAC5 XT’s
+12V output as shown in this diagram.
For a secondary device same connections would apply but the 12V for
2
nd
device is J6 pin 1 which would be connected to COM J15 pin 1 with
the Strike connected to NC J15 pin 2 and the Ground connection
would be connected to J6 pin 2.
1
2
3
4
1
2
3
4
1
2
3
4
J17
J3
J7
J8
J12
J1
J15
J16
J6
J18
J19
RAC5 XT PCB
N
O
NC
CO
M
G
ND F
IRE
G
ND 1
2V
_L
CK#
1
G
ND 1
2V
N
O
NC
CO
M
RE
_U
NL
#2
G
ND
RE
_U
NL
#1
1 (+) 2 (-) 3 (+) 4 (-)
1
2
3
4
1
2
3
2
1
1
2
3
12_L
C
K
#2 G
N
D
1 2 3 4
PWR GND GND PWR
RD#1
RD#2
READER 2
READER 1
1
2
3
4
J11
R
EX2
G
N
D
TA
MP
ER
GN
D
D
OOR
STA
T#
2 G
N
D
GN
D
R
EX#
1
GN
D
D
OOR
STA
T#
1 GN
D
GND LOW_BAT AC_FAIL
4 3 2 1
Figure 15 – Electromagnetic Lock Wiring
Mag Lock
12V GND
Fire Alarm
Bypass Wire
(See Note)
+12V Supply
For Locking Device
Note:
To automatically unlock the door in case of fire, remove the Fire Alarm
Bypass wire and connect J18 to the Fire Alarm panel as per Fire Alarm
Panel Wiring diagram (see Annex B, Figure 10).
In this case the Electromagnetic Lock MUST be powered from the
RAC5 XT’s +12V output as shown in this diagram.
For a secondary device same connections would apply but the 12V for
2
nd
device is J6 pin 1 which would be connected to COM J15 pin 1 with
the Mag Lock connected to NC J15 pin 2 and the Ground connection
would be connected to J6 pin 2.
1
2
3
4
1
2
3
4
1
2
3
4
J17
J3
J7
J8
J12
J1
J15
J16
J6
J18
J19
RAC5 XT PCB
N
O
NC
CO
M
G
ND F
IRE
G
ND 1
2V
_L
CK#
1
G
ND 1
2V
N
O
NC
CO
M
RE
_U
NL
#2
G
ND
RE
_U
NL
#1
1 (+) 2 (-) 3 (+) 4 (-)
1
2
3
4
1
2
3
2
1
1
2
3
12_L
C
K
#2 G
N
D
1 2 3 4
PWR GND GND PWR
RD#1
RD#2
READER 2
READER 1
1
2
3
4
J11
R
EX2
G
N
D
TA
MP
ER
GN
D
D
OOR
STA
T#
2 G
N
D
GN
D
R
EX#
1
GN
D
D
OOR
STA
T#
1 GN
D
GND LOW_BAT AC_FAIL
4 3 2 1