5.3  Set the fixture point

ATTENTION

Risk of cable damage

While setting the fixture points cables might 
be damaged.
•  Pay attention not to jam the connecting 

cables.

1. 

Open the fixed leaf until it clicks.

2. 

Unbolt the screws of the locking unit(s).

3. 

Open the door leaves to the desired hold open 
bracket.  
If the EMF is pushed to the end of the slide rail, 
the cable clips must be removed.

4. 

Unbolt the screws of the locking unit(s).

5. 

Place the door stop into the position of the fixture 
points selected.

5.4  Set the release force

ATTENTION

Risk of damage to the catching device 

 

Setting a release force too high may result 
in damage to the door hinges and the 
fastening elements of the door closing 
system. 
•  Set the release force depending on the 

door width and the selected size of the 
closing contact. 

•  According to the DIN EN 1155 the release 

force must not be less than 40 Nm at a 
door opening angle of 90° and not more 
than 120 Nm.

1. 

Set the release force without a tool.

2. 

Control the release force.

5.5  Mount the paneling

1. 

Attach the end caps.

2. 

Break off the marked gaps on the panelings. Pay 
attention that the correct side is broken off.

3. 

Mount the paneling of the glide rail.

5.6  Check the EMF

The EMF can be released manually or by cutting of 
the power supply.

5.6.1  Release EMF manually

1. 

Open the door leaf and lock it.

2. 

Pull on the door leaf.

 

‣ The door leaf is released and closes.

5.6.2  Delete EMF electronically

1. 

Open the door leaf and lock it.

2. 

Cut off the power supply (i.e. operation of the 
manual release button).

 

‣ The door leaf is released and closes.

5.7  Check the function of the 

catching device via the RMZ

CAUTION

Risk of eye and respiratory injury

•  Follow the application and safety 

instructions on the test gas and the safety 
data sheet.

1. 

Open the door and lock it.

2. 

Spray the test gas on the smoke detector 
according to the manufacturers’ instructions.

 

‣ The operation display switches to alarm (red).

 

‣ The door is closed.

During a manual reset: 

When the test gas has evaporated, press the reset 
button to activate the catching device again.

During an automatic reset:

The catching device will be activated again as soon as 
the test gas is evaporated. 
The door leaf may be locked after 30 seconds after 
releasing the catching device.

6  Closing the 

installation

If further structural work is carried out, protect the 
smoke detector against dust.

1. 

Switch the system to zero-potential.

2. 

Fit the provided dust cover.

3. 

Before the final start up, remove the dust cover 
and carry out a further functional check according 
to chapter 5.6.

6

G-EMR XEA

2018-11

dormakaba Installation manual

WN 059420 45532

Start up

Summary of Contents for G-EMR XEA

Page 1: ...3 3 Product description 4 3 1 RMZ 4 3 1 1 DIP switch on the RMZ 4 3 1 2 Clamp terminal assignment of the RMZ 4 3 1 3 Display of the operating status of the RMZ 4 3 2 EMF 4 3 3 Technical data 4 3 3 1 RMZ 4 3 3 2 EMF 4 4 Installation 5 4 1 Prepare the mounting of the slide rail 5 4 2 Mount the base 5 4 3 Mount the slide rail and RMZ 5 4 4 Mount the door closer 5 4 5 Establish electrical connections ...

Page 2: ...rovided documents Installation manual Connection diagrams RMZ RM ED Data sheet about the use of arrest systems General building approval 1 4 Symbols and abbreviations used 1 4 1 Safety instructions DANGER This signal word indicates a situation of immediate risk which will lead to death or serious injury if not averted CAUTION This signal word indicates a situation of potential risk which could lea...

Page 3: ... circuit breaker simultaneously serves as disconnect device to switch the RMZ to zero potential The transverse section of the mains supply line must only be a max 3 x 1 5 mm NYM 2 Safety DANGER Danger to life through electric current Works on electrical systems must only be carried out by skilled electricians Before starting work on electrical systems and equipment establish a zero potential condi...

Page 4: ...l manual release with terminating resistor 43 kOhm 10 7 NO Potential free changer low voltage SELV 24 V AC DC 1 A 8 NC 9 C 11 Potential free clamp 16 Bus 3 1 3 Display of the operating status of the RMZ Functions of the LEDs LED on LED off Operating display LED 1 green red operation green Alarm smoke detector red Alarm manual release button red Service display LED 2 yellow Maintenance due flashing...

Page 5: ...base 7 Screw the slide rail onto the base 8 Insert the connection cables of the EMF into the RMZ 4 4 Mount the door closer 1 Mount the door closer and lever to the door closer according to the enclosed instructions for the door leaf 2 Adjust the door closer 4 5 Establish electrical connections 1 Connect the 230 V AC connection cable For maintaining the protection category II protective insulation ...

Page 6: ...can be released manually or by cutting of the power supply 5 6 1 Release EMF manually 1 Open the door leaf and lock it 2 Pull on the door leaf The door leaf is released and closes 5 6 2 Delete EMF electronically 1 Open the door leaf and lock it 2 Cut off the power supply i e operation of the manual release button The door leaf is released and closes 5 7 Check the function of the catching device vi...

Page 7: ...est After installation an acceptance test is to be carried out according to the test book for catching devices The acceptance test must only be carried out by skilled staff that is certified for this by dormakaba Follow the details from the data sheet about the use of catching devices The acceptance test must be documented in the test book for catching devices 7 Operating 7 1 Open and lock door 1 ...

Page 8: ...dormakaba Deutschland GmbH DORMA Platz 1 58256 Ennepetal Germany T 49 2333 793 0 F 49 2333 793 4950 www dormakaba com 013558 Translation of the original manual subject to change without notice ...

Reviews: