5.3 Set the fixture point
ATTENTION
Risk of cable damage
While setting the fixture points cables might
be damaged.
• Pay attention not to jam the connecting
cables.
1.
Open the fixed leaf until it clicks.
2.
Unbolt the screws of the locking unit(s).
3.
Open the door leaves to the desired hold open
bracket.
If the EMF is pushed to the end of the slide rail,
the cable clips must be removed.
4.
Unbolt the screws of the locking unit(s).
5.
Place the door stop into the position of the fixture
points selected.
5.4 Set the release force
ATTENTION
Risk of damage to the catching device
Setting a release force too high may result
in damage to the door hinges and the
fastening elements of the door closing
system.
• Set the release force depending on the
door width and the selected size of the
closing contact.
• According to the DIN EN 1155 the release
force must not be less than 40 Nm at a
door opening angle of 90° and not more
than 120 Nm.
1.
Set the release force without a tool.
2.
Control the release force.
5.5 Mount the paneling
1.
Attach the end caps.
2.
Break off the marked gaps on the panelings. Pay
attention that the correct side is broken off.
3.
Mount the paneling of the glide rail.
5.6 Check the EMF
The EMF can be released manually or by cutting of
the power supply.
5.6.1 Release EMF manually
1.
Open the door leaf and lock it.
2.
Pull on the door leaf.
‣ The door leaf is released and closes.
5.6.2 Delete EMF electronically
1.
Open the door leaf and lock it.
2.
Cut off the power supply (i.e. operation of the
manual release button).
‣ The door leaf is released and closes.
5.7 Check the function of the
catching device via the RMZ
CAUTION
Risk of eye and respiratory injury
• Follow the application and safety
instructions on the test gas and the safety
data sheet.
1.
Open the door and lock it.
2.
Spray the test gas on the smoke detector
according to the manufacturers’ instructions.
‣ The operation display switches to alarm (red).
‣ The door is closed.
During a manual reset:
When the test gas has evaporated, press the reset
button to activate the catching device again.
During an automatic reset:
The catching device will be activated again as soon as
the test gas is evaporated.
The door leaf may be locked after 30 seconds after
releasing the catching device.
6 Closing the
installation
If further structural work is carried out, protect the
smoke detector against dust.
1.
Switch the system to zero-potential.
2.
Fit the provided dust cover.
3.
Before the final start up, remove the dust cover
and carry out a further functional check according
to chapter 5.6.
6
G-EMR XEA
2018-11
dormakaba Installation manual
WN 059420 45532
Start up