4 Installation
The mounting of the slide rail system takes place
directly on the base of the door lintel or optionally
with an additional mounting plate (extras).
4.1 Prepare the mounting of the
slide rail
The slide rail can be mounted in two different options:
Option
A
= Mounting on the hinge side DIN-L or on
the opposite hinge side DIN-R.
Option
B
= Mounting on the hinge side DIN-R or the
opposite hinge side DIN-L.
1.
Prepare the additional cover smoke detectors
and/or manual release buttons if necessary.
2.
Mark the fixing points for the closer and the slide
rails according to the hole pattern
A
or
B
.
3.
Drill the holes.
4.
Drill the holes for the connecting cables
Ø 12 mm and for the connection to required cover
smoke detectors and manual release button
Ø 10 mm.
5.
Lay the lines.
4.2 Mount the base
1.
Insert the connection cables to the appropriate
holes in the base.
2.
Mount the base.
4.3 Mount the slide rail and RMZ
Mounting option A
1.
Insert all cables into the intended openings.
2.
Screw the RMZ onto the base.
3.
Screw the slide rail onto the base.
4.
Insert the connection cables of the EMF into the
RMZ.
Mounting option B
1.
Turn the slide rail by 180° so that the end cap
connector is on the right side.
2.
Remove the end cap connector.
3.
Release the connection cable from the slide slip
surface and lead it through the slip surface to the
front.
4.
Clip the end cap connector on.
5.
Insert all cables into the intended openings.
6.
Screw the RMZ onto the base.
7.
Screw the slide rail onto the base.
8.
Insert the connection cables of the EMF into the
RMZ.
4.4 Mount the door closer
1.
Mount the door closer and lever to the door closer
according to the enclosed instructions for the
door leaf.
2.
Adjust the door closer.
4.5 Establish electrical
connections
1.
Connect the 230-V-AC-connection cable. For
maintaining the protection category II
(protective insulation), lay the 230-V-AC supply
double insulated up to the connecting terminal.
2.
Ensure the tension relief of the mains power
supply of the RMZ. The protective earth must not
be used electronically. Connect the provided
protective earth to the support terminal (PE).
3.
Close the touch protection.
4.
Screw the touch protection tightly.
Connect optional cover smoke detectors and/or
manual release buttons
5.
Connect the cover smoke detector and/or manual
release buttons to the RMZ according to the
enclosed connection diagrams.
6.
Take care with the terminating resistors
(43 kOhm).
5 Start up
5.1 Set the DIP switch
1.
Put the DIP switches in the appropriate position.
1 OFF = automatic reset
(delivery state)
ON = manual reset
Stick the provided label onto the cover
with this function type
2 OFF = 1-radial operation (line)
ON = 2-radial operation (star)
3 OFF = without optional cover smoke detector
ON = with optional cover smoke detector
4 OFF = without optional manual switch
ON = with optional manual release switch
2.
Press the reset button.
5.2 Laying the lines
1.
Remove the red protection cover from the smoke
detector unit.
2.
Turn on the on-site power supply 230 V AC.
‣ The operation display flashes green
5
G-EMR XEA
2018-11
dormakaba Installation manual
WN 059420 45532
Start up