3 Product description
The G-EMR XEA comprises the following components:
• Slide rail systems
• Built-in electromechanical locking device
• Smoke detection panel
The G-EMR XEA is intended for the mounting on the
hinge side or the opposite hinge side. The G-EMR XEA
is suitable for DIN-L and DIN-R doors.
3.1 RMZ
The RMZ supplies the connected electromechanical
locking device with 24-V-DC voltage. In the event of
an alarm or a power cut, the RMZ switches to zero-
potential (tripping) and the door closes. The new
arming takes place either through a manual or
automatic reset. Optional cover smoke detector RM
and manual release buttons HT may be connected to
the RMZ. 2 LEDs show the current operating status.
The configuration of the RMZ happens through the
DIP switch.
3.1.1 DIP switch on the RMZ
The functions of the RMZ are set via the DIP switch.
Changes are only accepted after pressing the reset
button (settings see chapter 5.1).
3.1.2 Clamp terminal assignment
of the RMZ
3 GND
Connection of external
detector with terminating
resistor
Total output
max. 9.8 W
12 + 24 V
14
1 +
Output 24 V DC
Catching device(s)
4 -
2
External manual release
with terminating resistor (43 kOhm)
10
7 NO
Potential free changer
low voltage (SELV)
24 V AC/DC, 1 A
8 NC
9 C
11
Potential free clamp
16
Bus
3.1.3 Display of the operating
status of the RMZ
Functions of the LEDs
LED on
LED off
Operating display LED 1 (green/red)
operation: green
Alarm smoke detector: red
Alarm manual release
button: red
Service display LED 2 (yellow)
Maintenance due: flashing
Soiling: flashing
Disturbance: duration
Disturbance: flashing
wrong wiring to the cover smoke detector/manual
release button
3.2 EMF
The EMF is an electromechanical locking mechanism
with adjustable release force, which enables locking
the door without spring back. After a cut-off of power
supply, the locking device disengages and the door will
be closed securely through the door closer.
3.3 Technical data
3.3.1 RMZ
Input:
230 V AC +10 %/–15 %
120 mA/28 VA/50 Hz
Output:
24 V DC/460 mA/11 W
Degree of protection:
IP 30
Protection category:
II
Smoke switch:
24 V DC/50 mA
Temperature:
-20 °C/+40 °C
Rel. Humidity:
max. 93 % without
condensation
3.3.2 EMF
Operating voltage:
24 V DC
Power consumption:
1.4 W
Duty cycle:
100 % ED
Release torque:
approx. 25 – 65 Nm at 90°
opening angle (dependent
on the set closing force on
the closer)
Door opening angle:
max. 140°
4
G-EMR XEA
2018-11
dormakaba Installation manual
WN 059420 45532
Installation