2.4  Prerequisites for the 

operation of catching devices

The use of catching devices is subject to special 
regulations by reason of official admission standards. 
These regulations refer in particular to the inspection, 
the continuing surveillance and the maintenance. 
Follow the details from the data sheet about the use 
of catching devices.
If the lower surface of the cover on one or both sides 
of the door is more than 1 m above the lintel bottom 
edge, an additional cover smoke detector must be 
mounted on each side of the door and must be 
connected with the RMZ. Measure the distance up to 
the smoke-impermeable ceiling. A separate 
verification of suitability is required for the respective 
fire / smoke protection door. 
Do not control any further alarm systems with the 
fire detector of the catching device, e.g. transmission 
device for fire alarms.

1

 RMZ

2

 EMF

3

 

Cover smoke detector

4

 

Manual release button for catching devices 
(optional). The manual release button must not 
be covered by the locked door.

2.5  Requirements of the electrical 

installation by the customer

A circuit breaker B-10A/B-16A must be present in the 
supply circuit. The circuit breaker simultaneously 
serves as disconnect device to switch the RMZ to 
zero-potential. The transverse section of the mains 
supply line must only be a max. 3 x 1.5 mm² (NYM).

2  Safety

DANGER

Danger to life through electric current

Works on electrical systems must only be 
carried out by skilled electricians.
•  Before starting work on electrical systems 

and equipment, establish a zero-potential 
condition and ensure this condition while 
carrying out the work.

2.1  Intended use

The catching device is used to keep open fire and 
smoke protection closures. Fire and smoke protection 
closures must meet the building regulation 
requirements ‘’self-locking’’. The electromechanical 
locking device is no substitution for a door stop. The 
locking device is released manually or via an external 
RMZ.

2.2  Foreseeable misuse

Do not control any further alarm systems with the 
fire detector of the catching device, e.g. transmission 
device for fire alarms.

2.3  Limitation of liability

The manufacturer does not assume liability for 
damages in the following events:
•  Nonobservance of this instruction.
•  A deviating application of the intended use.
•  The assignment of insufficiently skilled staff.
•  Unauthorized modifications.
•  Technical alterations.
•  The use of spare parts which are not authorized.

3

G-EMR XEA

2018-11

dormakaba Installation manual

WN 059420 45532

Safety

Summary of Contents for G-EMR XEA

Page 1: ...3 3 Product description 4 3 1 RMZ 4 3 1 1 DIP switch on the RMZ 4 3 1 2 Clamp terminal assignment of the RMZ 4 3 1 3 Display of the operating status of the RMZ 4 3 2 EMF 4 3 3 Technical data 4 3 3 1 RMZ 4 3 3 2 EMF 4 4 Installation 5 4 1 Prepare the mounting of the slide rail 5 4 2 Mount the base 5 4 3 Mount the slide rail and RMZ 5 4 4 Mount the door closer 5 4 5 Establish electrical connections ...

Page 2: ...rovided documents Installation manual Connection diagrams RMZ RM ED Data sheet about the use of arrest systems General building approval 1 4 Symbols and abbreviations used 1 4 1 Safety instructions DANGER This signal word indicates a situation of immediate risk which will lead to death or serious injury if not averted CAUTION This signal word indicates a situation of potential risk which could lea...

Page 3: ... circuit breaker simultaneously serves as disconnect device to switch the RMZ to zero potential The transverse section of the mains supply line must only be a max 3 x 1 5 mm NYM 2 Safety DANGER Danger to life through electric current Works on electrical systems must only be carried out by skilled electricians Before starting work on electrical systems and equipment establish a zero potential condi...

Page 4: ...l manual release with terminating resistor 43 kOhm 10 7 NO Potential free changer low voltage SELV 24 V AC DC 1 A 8 NC 9 C 11 Potential free clamp 16 Bus 3 1 3 Display of the operating status of the RMZ Functions of the LEDs LED on LED off Operating display LED 1 green red operation green Alarm smoke detector red Alarm manual release button red Service display LED 2 yellow Maintenance due flashing...

Page 5: ...base 7 Screw the slide rail onto the base 8 Insert the connection cables of the EMF into the RMZ 4 4 Mount the door closer 1 Mount the door closer and lever to the door closer according to the enclosed instructions for the door leaf 2 Adjust the door closer 4 5 Establish electrical connections 1 Connect the 230 V AC connection cable For maintaining the protection category II protective insulation ...

Page 6: ...can be released manually or by cutting of the power supply 5 6 1 Release EMF manually 1 Open the door leaf and lock it 2 Pull on the door leaf The door leaf is released and closes 5 6 2 Delete EMF electronically 1 Open the door leaf and lock it 2 Cut off the power supply i e operation of the manual release button The door leaf is released and closes 5 7 Check the function of the catching device vi...

Page 7: ...est After installation an acceptance test is to be carried out according to the test book for catching devices The acceptance test must only be carried out by skilled staff that is certified for this by dormakaba Follow the details from the data sheet about the use of catching devices The acceptance test must be documented in the test book for catching devices 7 Operating 7 1 Open and lock door 1 ...

Page 8: ...dormakaba Deutschland GmbH DORMA Platz 1 58256 Ennepetal Germany T 49 2333 793 0 F 49 2333 793 4950 www dormakaba com 013558 Translation of the original manual subject to change without notice ...

Reviews: