4  Installation

The mounting of the slide rail system takes place 
directly on the base of the door lintel or optionally 
with an additional mounting plate (extras). 

4.1  Prepare the mounting of the 

slide rail

The slide rail can be mounted in two different options:
Option 

A

 = Mounting on the hinge side DIN-L or on 

the opposite hinge side DIN-R.

Option 

B

 = Mounting on the hinge side DIN-R or the 

opposite hinge side DIN-L.

1. 

Prepare the additional cover smoke detectors 
and/or manual release buttons if necessary.

2. 

Mark the fixing points for the closer and the slide 
rails according to the hole pattern 

A

 or 

B

.

3. 

Drill the holes.

4. 

Drill the holes for the connecting cables  
Ø 12 mm and for the connection to required cover 
smoke detectors and manual release button 
Ø 10 mm.

5. 

 Lay  the  lines.

4.2  Mount the base

1. 

Insert the connection cables to the appropriate 
holes in the base.

2. 

Mount the base.

4.3  Mount the slide rail and RMZ

Mounting option A

1. 

Insert all cables into the intended openings.

2. 

Screw the RMZ onto the base.

3. 

Screw the slide rail onto the base.

4. 

Insert the connection cables of the EMF into the 
RMZ.

Mounting option B

1. 

Turn the slide rail by 180° so that the end cap 
connector is on the right side.

2. 

Remove the end cap connector.

3. 

Release the connection cable from the slide slip 
surface and lead it through the slip surface to the 
front.

4. 

Clip the end cap connector on.

5. 

Insert all cables into the intended openings.

6. 

Screw the RMZ onto the base.

7. 

Screw the slide rail onto the base. 

8. 

Insert the connection cables of the EMF into the 
RMZ.

4.4  Mount the door closer

1. 

Mount the door closer and lever to the door closer 
according to the enclosed instructions for the 
door leaf. 

2. 

Adjust the door closer.

4.5  Establish electrical 

connections

1. 

Connect the 230-V-AC-connection cable. For 
maintaining the protection category II   
(protective insulation), lay the 230-V-AC supply 
double insulated up to the connecting terminal.

2. 

Ensure the tension relief of the mains power 
supply of the RMZ. The protective earth must not 
be used electronically. Connect the provided 
protective earth to the support terminal (PE).

3. 

Close the touch protection.

4. 

Screw the touch protection tightly.

Connect optional cover smoke detectors and/or 
manual release buttons

5. 

Connect the cover smoke detector and/or manual 
release buttons to the RMZ according to the 
enclosed connection diagrams.

6. 

Take care with the terminating resistors 
(43 kOhm).

5  Start up

5.1  Set the DIP switch

1. 

Put the DIP switches in the appropriate position. 

 

1  OFF  =  automatic reset  

 

 

 

  (delivery state) 

 

 

ON   =  manual reset 

 

 

 

  Stick the provided label onto the cover  

 

 

 

  with this function type

 

2  OFF  =  1-radial operation (line) 

 

 

ON   =  2-radial operation (star)

 

3  OFF  =  without optional cover smoke detector 

 

 

ON   =  with optional cover smoke detector

 

4  OFF  =  without optional manual switch 

 

 

ON   =  with optional manual release switch 

2. 

Press the reset button.

5.2  Laying the lines

1. 

Remove the red protection cover from the smoke 
detector unit.  

2. 

Turn on the on-site power supply 230 V AC. 

 

‣ The operation display flashes green

5

G-EMR XEA

2018-11

dormakaba Installation manual

WN 059420 45532

Start up

Summary of Contents for G-EMR XEA

Page 1: ...3 3 Product description 4 3 1 RMZ 4 3 1 1 DIP switch on the RMZ 4 3 1 2 Clamp terminal assignment of the RMZ 4 3 1 3 Display of the operating status of the RMZ 4 3 2 EMF 4 3 3 Technical data 4 3 3 1 RMZ 4 3 3 2 EMF 4 4 Installation 5 4 1 Prepare the mounting of the slide rail 5 4 2 Mount the base 5 4 3 Mount the slide rail and RMZ 5 4 4 Mount the door closer 5 4 5 Establish electrical connections ...

Page 2: ...rovided documents Installation manual Connection diagrams RMZ RM ED Data sheet about the use of arrest systems General building approval 1 4 Symbols and abbreviations used 1 4 1 Safety instructions DANGER This signal word indicates a situation of immediate risk which will lead to death or serious injury if not averted CAUTION This signal word indicates a situation of potential risk which could lea...

Page 3: ... circuit breaker simultaneously serves as disconnect device to switch the RMZ to zero potential The transverse section of the mains supply line must only be a max 3 x 1 5 mm NYM 2 Safety DANGER Danger to life through electric current Works on electrical systems must only be carried out by skilled electricians Before starting work on electrical systems and equipment establish a zero potential condi...

Page 4: ...l manual release with terminating resistor 43 kOhm 10 7 NO Potential free changer low voltage SELV 24 V AC DC 1 A 8 NC 9 C 11 Potential free clamp 16 Bus 3 1 3 Display of the operating status of the RMZ Functions of the LEDs LED on LED off Operating display LED 1 green red operation green Alarm smoke detector red Alarm manual release button red Service display LED 2 yellow Maintenance due flashing...

Page 5: ...base 7 Screw the slide rail onto the base 8 Insert the connection cables of the EMF into the RMZ 4 4 Mount the door closer 1 Mount the door closer and lever to the door closer according to the enclosed instructions for the door leaf 2 Adjust the door closer 4 5 Establish electrical connections 1 Connect the 230 V AC connection cable For maintaining the protection category II protective insulation ...

Page 6: ...can be released manually or by cutting of the power supply 5 6 1 Release EMF manually 1 Open the door leaf and lock it 2 Pull on the door leaf The door leaf is released and closes 5 6 2 Delete EMF electronically 1 Open the door leaf and lock it 2 Cut off the power supply i e operation of the manual release button The door leaf is released and closes 5 7 Check the function of the catching device vi...

Page 7: ...est After installation an acceptance test is to be carried out according to the test book for catching devices The acceptance test must only be carried out by skilled staff that is certified for this by dormakaba Follow the details from the data sheet about the use of catching devices The acceptance test must be documented in the test book for catching devices 7 Operating 7 1 Open and lock door 1 ...

Page 8: ...dormakaba Deutschland GmbH DORMA Platz 1 58256 Ennepetal Germany T 49 2333 793 0 F 49 2333 793 4950 www dormakaba com 013558 Translation of the original manual subject to change without notice ...