15
OPERATOR PROGRAMMING
7. Type of reference point
NOTE:
When switching to another function, you must repeat steps 1-3 of the basic programming.
Press «+»
«7» will light, press «Р»
Pressing «+» or «-» choose the function value: «1» – microswitch,
«2» – stopper
Press «P» to save the settings
8. Remote control function for external lighting
Recording the remote transmitter button to control additional lighting.
Pressing «+» or «-» choose the function value: «Y» and confirm by pressing «P». After pressing the «P» button, the operator
automatically switches to the recording mode of the control button.
NOTE:
In the absence of control commands, the program exits transmitter recording mode automatically in 20 sec. The lighting
is on for an hour or until it is switched off by a second signal. Maximum permissible load for Ext.Lamp — 1 A.
Press «+»
«8» will light, press «Р»
Choose a button on the remote control and press it twice
Pressing «+» or «-» choose the function value: «Y» — on,
«n» — off (factory setting – «n»)
9. Remote control function for internal operator lighting
Recording the remote transmitter button to control internal operator lighting.
Pressing «+» or «-» choose the function value: «Y» and confirm by pressing «P». After pressing the «P» button, the operator
automatically switches to the recording mode of the control button.
10. Ventilation mode at high humidity
If the air humidity level reaches the set value when the door is closed, the door will partially open (ventilation mode).
If during ventilation the level of air humidity falls below the set value, than the door closes. If the level of air humidity rises
above the set value the door closes too. Next ventilation will start not earlier than in 30 minutes.
Press «+»
«9» wikk light, press «Р»
Choose a button on the remote control and press it twice
Pressing «+» or «-» choose the function value:
«Y» — on, «n» — off (factory setting – «n»)
Press «+»
«A» will light, press «Р»
Press «P» to save the settings
Pressing «+» or «-», select humidy level from 0 to 9, where «1» – 10%, «2» – 20%,
«3» – 30%, «4» – 40%, «5» – 50%, «6» – 60%, «7» – 70%, «8» – 80%, «9» – 90%, «0» – off
(factory setting – «0»)
NOTE:
In the absence of control commands, the program exits transmitter recording mode automatically in 20 sec. The lighting
is on for an hour or until it is switched off by a second signal.
NOTE:
If you press and hold the «P» button when the «A» item of the menu is activated, the display will show humidity level
in the room.