13
WARNING!
Exit from the menu items by pressing the «R» button leads to the failure to save the custom setting.
OPERATOR PROGRAMMING
9. Software version
Press «+»
«8» will light, press «Р»
P
+
-
The first digit is displaied
The second digit is displaied
When you enter the ninth menu item, two numbers are displayed sequentially. After the numbers are displayed, the program
returns to the main menu.
10. End of programming
Press «R» to exit programming mode. Programming is over.
NOTE:
You can exit any point of the programming.
Menu Function description
Default
1
Distant remote transmitter programming: «Y» – on, «n» – off
Y
2
Absolute cycle counter
0
3
Prohibition of control commands for closing: «Y» – on, «n» – off
n
4
Type of safety device: «0» – external, «1» – built-in
0
5
Door opening height during ventilation: «0» – 200 mm, «1» – 1000 mm
0
6
Force adjustment: «1» – minimum, «6» – maximum
3
7
Reference point type: «1» – microswitch, «2» – stopper.
1
8
Remote control function for external lighting: «Y» – on, «n» – off
n
9
Remote control function for internal operator lighting: «Y» – on, «n» – off
n
А
Ventilation mode at high humidity
n
6.4. ADVANCED PROGRAMMING
To enter the advanced programming menu, press and hold the «P» button for 15 seconds. The display will light up «1».
1. Distant remote transmitter programming
Press and hold «P» for 15 sec
«1» will light, press «Р»
Pressing «+» or «-» choose the function value: «Y» — on, «n» — off,
(factory setting — «n»)
Press «P» to save the settings