Delta P Plus Control

 4

Parameters Description

Setting 

Range

Factory 

Default

Units

Function

ALL

ALL - Combines differential pressure (Delta 
P) based cleaning with downtime  cleaning 
ON/OFF selectable from keypad.

P 6

Mode Select

DTC

ALL

- -

DTC - Filters downtime cleaned only, not 
based on filter Delta P.

DFF

DFF - Filter cleaning based on Delta P with 
downtime cleaning not available.

P 7

Display Units 
0 = in. w.g. 
1 = daPa

0 - 1

0

- -

Selects units of measure for the  
digital display.

P 8

Downtime Start 
Relay

30 - 99

30

Seconds

Adjustable time lag between the pressure 
dropping below the value set in parameter 
P 11 and the start of downtime cleaning.

P 9

Downtime 
Pressure Enable 
Relay

30 - 99

30

Seconds

Adjustable time required to be above the 
value set as the High Set Point (Hi) before 
the downtime feature is enabled.

P 10

Downtime 
Cleaning Time

1 - 999

10

Minutes

The amount of time the downtime cleaning 
will continue once the time set in P 9 
expires.*

P 11

Downtime Start 
Pressure

0 - 9.6 (245) 0.3 (13)

In. Water 

(daPa)

The falling pressure that triggers the 
downtime cleaning sequence. **

P 12

Pressure Sensor 
Input Filtering

0 - 2

1

- -

Sets the time used for Delta P value 
averaging (0 = 250 ms, 1 = 2.5 sec, 2 = 10 
sec).

P 13

Reset to Factory 
Defaults

0 - 1

0

- -

0 = No Reset 

 

 

 

 

1 = Reset

P 14

Zero Offset

0 - 1

0

- -

0 = No Operations 

 

 

 

1 = Offset and Displayed Zero

P 15

Software Version

- -

- -

- -

P 16

Password

- -

- -

- -

Factory password, no user adjustable 
items in subsequent parameters.

* If the downtime cleaning sequence is in progress and the pressure drop indicates a fan restart, the cleaning sequence will end.

** If P 11 is set as equal to or greater than the Lo value, the Lo value will automatically increase 0.2” above the P 11 value.

Summary of Contents for Delta P Plus

Page 1: ...roperty of the owner Leave with the unit when set up and start up are complete Donaldson Company reserves the right to change design and specifications without prior notice Illustrations are for refer...

Page 2: ...ach of these responsibilities are met As a manufacturer and supplier of Industrial Filtration Products Donaldson can assist process owners operators in the selection of filtration technologies However...

Page 3: ..._______ Other_________________________________________________________________________________ DANGER indicates a hazardous situation which if not avoided will result in death or serious injury WARNIN...

Page 4: ...taining the differential pressure drop in a specified range then initiating a down time cleaning cycle when the differential pressure drop approaches zero The downtime cleaning function can be toggled...

Page 5: ...al and local codes Turn power off and lock out electrical power sources before performing service or maintenance work Do not install in classified hazardous atmospheres without an enclosure rated for...

Page 6: ...e differential pressure drop value used to start the pulse cleaning cycle 4 0 w g is a typical initial value 3 Press the MENU key three times AL appears Press the set key and the current value appears...

Page 7: ...e set as the High Set Point Hi before the downtime feature is enabled P 10 Downtime Cleaning Time 1 999 10 Minutes The amount of time the downtime cleaning will continue once the time set in P 9 expir...

Page 8: ...th a short length of tubing 3 Use the Menu key to select PAS 4 Press SET then use the arrow keys to display 4 press SET again 5 Press the MENU key repeatedly until you reach P 14 6 Press SET then use...

Page 9: ...Delta P Plus Control 6 high pressure port low pressure port clean air plenum dirty air plenum Delta P Plus Control Installation...

Page 10: ...switch Closing the switch turns the alarm OFF Internal Alarm Disable J5 To disable the alarm internally remove the jumper on MODE Jumper Block J5 located on the lower right quadrant of the circuit boa...

Page 11: ...R31 R32 R25 R39 R29 R21 R22 R23 C11 C12 TB2 3 2 1 J1 in mm L1 L2 1 2 TB1 115 230 V input W1 W2 W3 115V 230V 115V UP DOWN CP4 CP5 CP2 U4 U8 C15 high Alarm C5 R34 R16 R15 R19 R14 Cleaning Alarm CP3 U3 C...

Page 12: ...the pressure switch on the timer board to Terminals 7 and 8 on TB3 Faulty relay Using a multimeter test relay for proper closure Replace if necessary Pressure tubing disconnected ruptured or plugged...

Page 13: ...mer board s LED display If not illuminated check the supply voltage to the timer board Check the fuse on the timer board Replace if necessary Timer board defective If LEd is iluminated observe the out...

Page 14: ...reset 3 4 5 6 R26 R28 R31 R32 R25 R39 R29 R21 R22 R23 C11 C12 TB2 3 2 1 J1 in mm L1 L2 1 2 TB1 115 230 V input W1 W2 W3 115V 230V 115V UP DOWN CP4 CP5 CP2 U4 U8 C15 high Alarm C5 R34 R16 R15 R19 R14...

Page 15: ......