Optional Settings

See Printed Circuit Board illustration.

230 VAC Power Supply

To operate at 230 VAC, remove two jumpers labeled W1 
and W3. Reinsert one of the jumpers in position W2.

Change from English to Metric (SI) Units

1.  Turn power to the Delta P Plus Control ON.
2.  Use the Menu key to select PAS.
3.  Press SET, then use the arrow keys to display “4”, 

press SET again.

4.  Press the MENU key repeatedly until you reach P 6.
5.  Press SET, then use the arrow keys to display “0”, 

press SET again.

6.  After 10 seconds with no further button action, the 

display will return to reading the pressure.

Disable Setpoint Adjustment

To restrict setpoint changes, install a jumper wire across 
the PROG. DISABLE terminals (3 & 4) on Terminal Block 
2, TB2. The current settings will still be displayed, but 
no changes can be made until the jumper is removed. 
Interrupting the jumper with a key-operated, normally-
closed switch installed in the enclosure door provides 
temporary access to the setting functions without 
opening the door.

External Alarm Reset / Disable (TB2, 
Terminal 5 & 6)

If desired, wire the ARM RESET terminals (5 & 6) on 
Terminal Block 2, TB2, to a key-operated, normally-open 
switch. Closing the switch turns the alarm OFF.

Internal Alarm Disable (J5)

To disable the alarm internally, remove the jumper on 
MODE Jumper Block J5, located on the lower-right 
quadrant of the circuit board. Disabling the alarm relay 
reduces the alarm function to the ALARM LED visual 
display only. 

Hi/Lo Control (TB3, Terminals 7, 8, & 9)

Per the wiring diagram supplied with the controller, the 
Hi/Lo terminals are connected to the pressure switch 
input on the timer board.  In most cases this connection 
is made at the factory.
Terminal 8 is common, terminal 7 is normally open, and 
terminal 9 is normally closed.

Auxiliary Relay Output (TB3, Terminals 10, 
11, & 12)

1.  If the jumper on the MODE Jumper Block J5 is not 

installed, the auxiliary relay output will not function.

2.   If the jumper is installed in the ALARM mode 

position, the auxiliary relay output activates based on 
the setting of the ALARM setpoint. 

3.   If the jumper is installed in the SLAVE mode position, 

the auxiliary relay output activates in parallel with 
the HI/LO CONTROL relay.

Terminal 11 is common, terminal 10 is normally open, and 
terminal 12 is normally closed.

Analog Output (TB4, Terminals 13 & 14)

Terminals 13 & 14 on Terminal Block 4, TB4, in the 
upper-left quadrant of the circuit board, provide a 4 to 
20 mA output proportional to the 0-to-maximum span 
of the pressure sensor. This circuit requires a 500 ohm 
maximum load.

Summary of Contents for Delta P Plus

Page 1: ...roperty of the owner Leave with the unit when set up and start up are complete Donaldson Company reserves the right to change design and specifications without prior notice Illustrations are for refer...

Page 2: ...ach of these responsibilities are met As a manufacturer and supplier of Industrial Filtration Products Donaldson can assist process owners operators in the selection of filtration technologies However...

Page 3: ..._______ Other_________________________________________________________________________________ DANGER indicates a hazardous situation which if not avoided will result in death or serious injury WARNIN...

Page 4: ...taining the differential pressure drop in a specified range then initiating a down time cleaning cycle when the differential pressure drop approaches zero The downtime cleaning function can be toggled...

Page 5: ...al and local codes Turn power off and lock out electrical power sources before performing service or maintenance work Do not install in classified hazardous atmospheres without an enclosure rated for...

Page 6: ...e differential pressure drop value used to start the pulse cleaning cycle 4 0 w g is a typical initial value 3 Press the MENU key three times AL appears Press the set key and the current value appears...

Page 7: ...e set as the High Set Point Hi before the downtime feature is enabled P 10 Downtime Cleaning Time 1 999 10 Minutes The amount of time the downtime cleaning will continue once the time set in P 9 expir...

Page 8: ...th a short length of tubing 3 Use the Menu key to select PAS 4 Press SET then use the arrow keys to display 4 press SET again 5 Press the MENU key repeatedly until you reach P 14 6 Press SET then use...

Page 9: ...Delta P Plus Control 6 high pressure port low pressure port clean air plenum dirty air plenum Delta P Plus Control Installation...

Page 10: ...switch Closing the switch turns the alarm OFF Internal Alarm Disable J5 To disable the alarm internally remove the jumper on MODE Jumper Block J5 located on the lower right quadrant of the circuit boa...

Page 11: ...R31 R32 R25 R39 R29 R21 R22 R23 C11 C12 TB2 3 2 1 J1 in mm L1 L2 1 2 TB1 115 230 V input W1 W2 W3 115V 230V 115V UP DOWN CP4 CP5 CP2 U4 U8 C15 high Alarm C5 R34 R16 R15 R19 R14 Cleaning Alarm CP3 U3 C...

Page 12: ...the pressure switch on the timer board to Terminals 7 and 8 on TB3 Faulty relay Using a multimeter test relay for proper closure Replace if necessary Pressure tubing disconnected ruptured or plugged...

Page 13: ...mer board s LED display If not illuminated check the supply voltage to the timer board Check the fuse on the timer board Replace if necessary Timer board defective If LEd is iluminated observe the out...

Page 14: ...reset 3 4 5 6 R26 R28 R31 R32 R25 R39 R29 R21 R22 R23 C11 C12 TB2 3 2 1 J1 in mm L1 L2 1 2 TB1 115 230 V input W1 W2 W3 115V 230V 115V UP DOWN CP4 CP5 CP2 U4 U8 C15 high Alarm C5 R34 R16 R15 R19 R14...

Page 15: ......

Page 16: ...to corrosion abrasion normal wear and tear product modification or product misapplication Donaldson also makes no warranty whatsoever as to any goods manufactured or supplied by others including elec...

Reviews: