Troubleshooting

Problem

Probable Cause

Remedy

No display on the  
Delta P Plus Control

No power to the control

Use a voltmeter to check for voltage at Terminal TB1.

Fuse blown

Check the fuse in the F1 fuse tower. Replace if 
necessary.

Display on the Delta P 
Plus control does not 
read zero when at rest

Out of calibration

Disconnect pressure tubing. See Delta P Plus Control 
Calibration.

With collector discharging 
outside, differential pressure is 
present from indoor to outdoor

Recalibrate with the pressure tubing attached as 
described in Delta P Plus Control Calibration.

Display reads “_ _ _”

Pressure out of the allowable 
range

Check that high and low pressure tubing is attached 
and not leaking. Use a differential pressure 
measurement device to verify that the actual 
pressure does not exceed 20 “wg.

Delta P Plus Control ON, 
but cleaning system 
does not start

Not wired to the timing board 
correctly

Connect the pressure switch on the timer board to 
Terminals 7 and 8 on TB3.

Faulty relay

Using a multimeter, test relay for proper closure. 
Replace if necessary.

Pressure tubing disconnected, 
ruptured, or plugged

Check tubing for kinks, breaks, contamination, or 
loose connections.

Pulse cleaning never 
stops

Pressure switch terminals on 
the timer board jumpered

Remove jumper wire on solid-state timer board 
before wirng to Delta P Plus Control.

Pressure switch not wired to the 
timer board corrrectly

Connect the pressure switch on the timer board to 
terminal 7 (normally open) and Terminal 8 (common) 
on TB3.

High or low setpoint not 
adjusted for system conditions

Adjust setpoints to current conditions. See Setpoint 
Adjustment.

Pressure tubing disconnected, 
ruptured or plugged.

Check tubing for kinks, breaks, contamination, or 
loose connections.

Alarm light is ON

Alarm setpoint too low

Adjust to a higher value.

Excess pressure drop

Check cleaning system and compressed-air supply. 
Replace filter cartridges if filters do not clean down.

Pressure tubing disconnected, 
ruptured, or plugged

Check tubing for kinks, breaks, contamination, or 
loose connections.

Summary of Contents for Delta P Plus

Page 1: ...roperty of the owner Leave with the unit when set up and start up are complete Donaldson Company reserves the right to change design and specifications without prior notice Illustrations are for refer...

Page 2: ...ach of these responsibilities are met As a manufacturer and supplier of Industrial Filtration Products Donaldson can assist process owners operators in the selection of filtration technologies However...

Page 3: ..._______ Other_________________________________________________________________________________ DANGER indicates a hazardous situation which if not avoided will result in death or serious injury WARNIN...

Page 4: ...taining the differential pressure drop in a specified range then initiating a down time cleaning cycle when the differential pressure drop approaches zero The downtime cleaning function can be toggled...

Page 5: ...al and local codes Turn power off and lock out electrical power sources before performing service or maintenance work Do not install in classified hazardous atmospheres without an enclosure rated for...

Page 6: ...e differential pressure drop value used to start the pulse cleaning cycle 4 0 w g is a typical initial value 3 Press the MENU key three times AL appears Press the set key and the current value appears...

Page 7: ...e set as the High Set Point Hi before the downtime feature is enabled P 10 Downtime Cleaning Time 1 999 10 Minutes The amount of time the downtime cleaning will continue once the time set in P 9 expir...

Page 8: ...th a short length of tubing 3 Use the Menu key to select PAS 4 Press SET then use the arrow keys to display 4 press SET again 5 Press the MENU key repeatedly until you reach P 14 6 Press SET then use...

Page 9: ...Delta P Plus Control 6 high pressure port low pressure port clean air plenum dirty air plenum Delta P Plus Control Installation...

Page 10: ...switch Closing the switch turns the alarm OFF Internal Alarm Disable J5 To disable the alarm internally remove the jumper on MODE Jumper Block J5 located on the lower right quadrant of the circuit boa...

Page 11: ...R31 R32 R25 R39 R29 R21 R22 R23 C11 C12 TB2 3 2 1 J1 in mm L1 L2 1 2 TB1 115 230 V input W1 W2 W3 115V 230V 115V UP DOWN CP4 CP5 CP2 U4 U8 C15 high Alarm C5 R34 R16 R15 R19 R14 Cleaning Alarm CP3 U3 C...

Page 12: ...the pressure switch on the timer board to Terminals 7 and 8 on TB3 Faulty relay Using a multimeter test relay for proper closure Replace if necessary Pressure tubing disconnected ruptured or plugged...

Page 13: ...mer board s LED display If not illuminated check the supply voltage to the timer board Check the fuse on the timer board Replace if necessary Timer board defective If LEd is iluminated observe the out...

Page 14: ...reset 3 4 5 6 R26 R28 R31 R32 R25 R39 R29 R21 R22 R23 C11 C12 TB2 3 2 1 J1 in mm L1 L2 1 2 TB1 115 230 V input W1 W2 W3 115V 230V 115V UP DOWN CP4 CP5 CP2 U4 U8 C15 high Alarm C5 R34 R16 R15 R19 R14...

Page 15: ......

Page 16: ...to corrosion abrasion normal wear and tear product modification or product misapplication Donaldson also makes no warranty whatsoever as to any goods manufactured or supplied by others including elec...

Reviews: