FUSION HE
12
5.4
Heating expansion vessel
The
DUAL CLIMA
heat pump incorporates an expansion vessel with capacity for 2 litres by default.
In the event that it is necessary to increase this capacity, due to the total amount of water in the
Heating/Cooling system, the
FUSION
hydraulic module allows the installation of an 8-litre
expansion vessel kit (optionally supplied) inside it.
For its correct assembly inside the
FUSION
module, once it is ensured that the heating/cooling
system is empty, please carefully follow the steps indicated in the following figures:
1.-
Cut the insulation to access the plug of the expansion
vessel socket, located above the water filter (see
“List of
components”)
. Cu the area in such a manner that the
removed insulation can be reused.
2.-
Disassemble the cap from the expansion vessel socket.
3.-
Place the expansion vessel under the base of the bottom
right of the module, as indicated in the figure, with the
socket facing towards the front and upwards.
4.-
Fix the expansion vessel to the base of the module, using
the support plate and the screws supplied with the kit, as
indicated in the figure.
5.-
Connect the expansion vessel and the socket provided in
the module, using the hose supplied with the kit, making
sure to seal both ends of the connection correctly.
6.-
Replace the insulation around the entire area where it was
previously removed, making sure to cover all the
components exposed to possible condensation.
IMPORTANT: Before proceeding
with the assembly of the expansion vessel kit inside the
module, make sure that the Heating/Cooling system is empty.