DOMEL
EC – Controller Compacto
V2.0, July 2014
Operating and installation Instructions
20
101
SO output signal
-10000..2
0.01%
<1: Manual output value
(-10000=100%)
1: Motor RPM
2: Set Point
>2: reserved
1
102 - 106
RESERVED
107
AN1Max
0..1000
0.01V
Voltage for maximum setpoint.
Transfer function is inverted if
AN1Max < AN1Min.
1
108
AN1Min
0..1000
0.01V
Voltage for minimum setpoint
1
109
AN1Stop
0..1000
0.01V
0: disable stop
AN1Stop >0: Stop threshold voltage.
1
Input Registers
Address
Function
Range
Resolution
Description
0
HW Version
1
Hardware version
1
FW Version
1
Firmware version
2..3
RESERVED
4
Speed
0..32767
1
RPM
5
Controller temperature
-50..150
0.01
°C
6
UDC
0.1
DC Bus voltage in V
7
Stator IRMS
0.001
RMS Stator current in A
8
Power
0.1
W
9
Analogue1
-300..2000
0.01V
Analogue input 1 voltage
10
Analogue2
-300..2000
0.01V
Analogue input 2 voltage
11
Analogue POT
-300..2000
0.01V
Analogue POT voltage
12
SO voltage
-300..2000
0.01V
SO output voltage
13
SO current
-300..3300
0.01mA
SO output current
14
IAC
0.001
Line RMS current in A
15 - 18
RESERVED
19
Error Code
0..7, -1
Red LED error codes (priority in the order
below):
7 = motor failed to start repeatedly
6 = under or overvoltage
5 = motor misconnected/faulty
4 = internal frequency converter fault
3 = temperature protection active
2 = active overcurrent protection
1 = slow blink = standby
-1 = fast blink (fire activated)
0 = always on (operating normally)
20
Fire Minutes
Minutes under fire mode
21
Fire Days
Days under fire mode
22
Fire Cycles
Fire activated counter