DOMEL
EC – Controller Compacto
V2.0, July 2014
Operating and installation Instructions
18
27
OvermodReg
0-1
Over modulation reached. Converter can
no longer supply the voltage required by
motor.
28
RegenReg
0-1
Motor is in regeneration. Speed increased
to prevent DC link over voltage
29
IphaseReg
0-1
RMS motor phase current limit reached
30
SyncReg
0-1
Motor is still in Synchronous mode
31
RESERVED
ACCESS LEVEL:
0
– read only
1
– basic user settings
2
– service settings
Holding Registers
Address
Function
Range
Resolution
Description
LEVEL
0
Set point
0..10000
0,01%
Performance set point for speed
depends on operation mode.
1
1
Direction
0..65535
1
Motor direction:
0: clockwise rotation.
>0: anti-clockwise rotation
2
2
Maximum Speed
MinRPM..
MaxRPM[level+1]
1
Max rpm allowed in normal
operation. External control will use
this as set point maximum. Value
from level above current is used as
Max.
1
3
Fire Speed
0.67*RPM_Max to
RPM_Max
1
RPM when fire mode is active
(2/3*RPM_Max to RPM_Max)
2
4
Minimal Speed
200 RPM to Max
RPM
1
Minimal allowed speed
1
5
Password
0..32767
0: level 0, all settings locked (default
password for level 1)
1: password for current level will be
disabled with 10020
10000: store values to EEPROM at
current level (will override lower
levels)
10001: restore values from
EEPROM (last saved values)
10002: restore default values from
one level above current
10020: set previous value as
password
(will not be accepted if desired
password matches 10000..11000 or
level is <1)
See 1: for how to disable password
When level is changed, stored
values for the level will be loaded
1