B. Test Templates
72A-2570-01 Rev. K 07/2011
B-3
Autotransformers
* Indicates short-circuit tests where the terminals are shorted together with three
sets of jumpers, to provide symmetry (X1-X2, X2-X3, X3-X1) OR (Y1-Y2,
Y2-Y3, Y3-Y1). The neutral is not included for 3
wye connections but may
be included for 1
test connections.
Table B.2 Autotransformer without Tertiary or with Buried Tertiary —
9 Tests
Test Type
Test #
3
1
Series Winding (OC)
All Other Terminals
Floating
Test 1
H1-X1
H1-X1
Test 2
H2-X2
Test 3
H3-X3
Common Winding (OC)
All Other Terminals
Floating
Test 4
X1-H0X0
X1-H0X0
Test 5
X2-H0X0
Test 6
X3-H0X0
Short Circuit (SC)
High (H) to Low (L)
Short [X1-X2-X3-X1]*
Test 7
H1-H0X0
H1-H0X0
Short
[X1-H0X0]*
Test 8
H2-H0X0
Test 9
H3-H0X0
Table B.3 Autotransformer With Tertiary — 18 Tests
Test Type
Test #
3
1
Series Winding (OC)
All Other Terminals Floating
Test 1
H1-X1
H1-X1
Test 2
H2-X2
Test 3
H3-X3
Common Winding (OC)
All Other Terminals Floating
Test 4
X1-H0X0
X1-H0X0
Test 5
X2-H0X0
Test 6
X3-H0X0
Tertiary Winding (OC)
All Other Terminals Floating
Test 7
Y1-Y3
Y1-Y2
(Y1-Y0)
Test 8
Y2-Y1
Test 9
Y3-Y2
Summary of Contents for SFRA
Page 12: ...Sweep Frequency Response Analyzer SFRA User Guide xii 72A 2570 01 Rev K 07 2011...
Page 14: ...Sweep Frequency Response Analyzer SFRA User Guide xiv 72A 2570 01 Rev K 07 2011...
Page 24: ...Sweep Frequency Response Analyzer SFRA User Guide 2 4 72A 2570 01 Rev K 07 2011...
Page 56: ...Sweep Frequency Response Analyzer SFRA User Guide 3 32 72A 2570 01 Rev K 07 2011...
Page 78: ...Sweep Frequency Response Analyzer SFRA User Guide 5 18 72A 2570 01 Rev K 07 2011...
Page 98: ...Sweep Frequency Response Analyzer SFRA User Guide A 20 72A 2570 01 Rev K 07 2011...
Page 110: ...Sweep Frequency Response Analyzer SFRA User Guide C 6 72A 2570 01 Rev K 07 2011...
Page 116: ...Sweep Frequency Response Analyzer SFRA User Guide D 6 72A 2570 01 Rev K 07 2011...