DMP Electronics XTLplusINT Series Installation And Programming Manual Download Page 1

DIGITAL MONITORING PRODUCTS, INC.

INTERNATIONAL PROGRAMMING GUIDE

Summary of Contents for XTLplusINT Series

Page 1: ...DIGITAL MONITORING PRODUCTS INC INTERNATIONAL PROGRAMMING GUIDE...

Page 2: ...he following booklet prepared by the Federal Communications Commission helpful How to identify and Resolve Radio TV Interference Problems This booklet is available from the U S Government Printing Off...

Page 3: ...n 5 LED OPERATION Backlit Logo 6 RESET BUTTON Description 6 TAMPER BUTTON Description 6 PROG PROGRAMMING CONNECTION Description 6 ON BOARD 1100INT SERIES WIRELESS Wireless Antenna 6 Wireless LED Opera...

Page 4: ...r 15 Zone Number 15 Zone Name 15 Zone Type 15 Area Assignment 15 Serial Number Entry 15 Stop 15 COMMUNICATION Communication 16 Account Number 16 Transmission Delay 16 Communication Type 16 Backup Cell...

Page 5: ...Options 22 Remote Key 22 Remote Disarm 22 App Key For EASYconnect only 22 SYSTEM REPORTS System Reports 23 Opening Closing Reports 23 Abort Reports 23 Zone Restoral Reports 23 Bypass Reports 23 Code C...

Page 6: ...re Alarm Output 30 Fire Trouble Output 30 Ambush Output 30 Begin Exit Output 30 End Exit Output 30 Ready Output 30 Armed Output 30 Disarmed Output 30 Burglary Output 30 Arm Alarm Output 30 Heat Saver...

Page 7: ...ut Number 39 Output Action 39 Alarm Action 39 Disarmed Open 39 Message To Transmit 39 Output Number 40 Output Action 40 Swinger Bypass 40 Prewarn Address 40 Chime 40 Entry Delay 40 Cross Zone 41 Prior...

Page 8: ...entral Station Receivers Keypads You can associate up to seven 9862INT Series Graphic Touchscreen Keypads Number of Zones XTLplusINT has 99 wireless initiating zones numbered 1 99 Zone and Output numb...

Page 9: ...s installation standard or a National Recognized Testing Laboratory certificated system please see the Listed Compliance Specifications section near the end of this guide for additional instructions S...

Page 10: ...wireless transmitters or repeaters It is not necessary to remove the PCB when installing the enclosure Primary Power Supply DC Input Mount the panel near a wall outlet for the Model 372 500 W plug in...

Page 11: ...2 Loosen the top PCB snaps 3 Lean the panel PCB forward and lift out from the bottom PCB snaps 4 Remove and properly dispose of the used battery Caution Risk of fire explosion and burns Do not disass...

Page 12: ...el s built in wireless receiver operates with DMP 1100INT Series transmitters See section 3 1 for a list of accessory devices Wireless LED Operation The wireless LEDs are located in the upper right of...

Page 13: ...elease the LOAD button 6 After the firmware version is updated the green LED will be steady 7 Press and hold the Reset button remove the 401 then release the Reset button to resume normal operation ON...

Page 14: ...and ending a programming session Getting Started Ground yourself before handling the panel Touch any grounded metal before touching the panel to discharge static The panel should be completely install...

Page 15: ...following special keys or areas are common to all DMP keypads COMMAND CMD Key Pressing CMD allows you to go forward through the programming menu and through each step of a programming sec tion As you...

Page 16: ...e a programming option that requires a NO or YES response press the select key for the response not selected See Figure 13 For example if the current option is selected as YES and you want to change i...

Page 17: ...f you lose or forget the lockout code the panel must be sent back to the factory to be reset There is no field option for gaining access to the panel without a valid lockout code Reset Timeout The XTL...

Page 18: ...ct YES clears the events memory Clear Zone Information NO leaves existing zone information intact YES clears the zone information for all zones Clear Communication Options NO leaves existing communica...

Page 19: ...Enter the number 0 23 that indicates the Greenwich Time zone GMT where the panel is located See System Options Weather Postal Code Enter the zip code of the panel at this option See System Options En...

Page 20: ...provided in Diagnostics Function located in the Appendix Backup Cellular Backup Cellular option is available if COMM TYPE is set for WIFI The Backup Cellular tries to send the message after the main...

Page 21: ...Restoral Force Armed Late to Close and Fault reports to be sent to this receiver Default is YES Opening Closing and User Reports YES enables Opening Closing Code Changes and Bypass reports by user to...

Page 22: ...ables the Recall Test report to be sent to this receiver Default is NO First IP Address Enter the first primary IP address where the panel sends network or cellular information Enter all 12 digits and...

Page 23: ...work router to which you are attempting to connect SEARCHING displays for up to two minutes or until connected to the WPS enabled router Refer to the router s instruction manual for sending a security...

Page 24: ...hen successful W L SECURITY displays Select the security type based on the network router programming The default network security type is WPA PSK Press any select area to display the other security o...

Page 25: ...anel to resolve domain names into IP addresses The default address is 192 168 000 001 The DHCP programming in the panel must be set to NO Programming Port Enter the programming port number The program...

Page 26: ...vices Default is NO The door device type is only for devices 2 8 on XTL International Series panels Network Display Only Select YES to use a 7463 network keypad Select NO to use a wired or wireless ke...

Page 27: ...ccess All panels are shipped from the factory with the Remote Key preset as blank To enter a new Remote Key press any select area and enter any combination of up to 8 digits The numbers you enter appe...

Page 28: ...larm or trouble condition DISARM The panel sends zone restoral reports when a zone that has restored from an alarm or trouble is disarmed Twenty four hour zones send restorals immediately Bypass Repor...

Page 29: ...sage is sent to the central station Default is 0 which disables the Early to Close option Entry Check in Protection If YES is selected this enables the panel to send a Serial 1 check in message when a...

Page 30: ...keypad If within five seconds a valid user code is not entered or an invalid user code is entered the prewarn tone begins sounding again Fifteen seconds must elapse before entering a digit silences t...

Page 31: ...eration restores a bypassed zone Entering 0 zero disables this function Default is 2 How it works The panel hour timer starts at 59 minutes past the hour If the hour timer expires before the trip coun...

Page 32: ...o Seoul 3 Buenos Aires Georgetown Brasilia Rio de Janeiro 16 Hong Kong Singapore 4 Atlantic Time Canada Caracas La Paz Santiago 17 Bangkok Hanoi 5 Eastern Time US Canada Bogota Lima Arequipa 18 Dhaka...

Page 33: ...NONE Enter Passphrase ENTER PASSPHRASE displays if you select ALL or BOTH for wireless encryption In order for the panel to support encrypted 1100INT Series wireless devices a passphrase must be ente...

Page 34: ...second and then displays the ALL SYSTEM ON message If communication fails the message LOCAL ALARM ONLY appears Bell Output Enter the output number 51 54 61 64 when it is necessary to follow the on an...

Page 35: ...Series Installation and Programming Guide 28 Auxiliary 2 Defines Bell Action for Auxiliary 2 Type Zones The default is set at N Carbon Monoxide CO Defines Bell Action for Carbon Monoxide CO Type Zone...

Page 36: ...Reset option Enter 0 zero to disable this output Begin Exit Output This output Favorite turns on any time an exit delay time starts The output turns off when the system arms or when the arming has be...

Page 37: ...d ALL or AWAY When the system is disarmed the thermostats return to their previous settings The range is 55 95 degrees Enter 0 zero to disable Cool Saver Temperature Enter the desired temperature sett...

Page 38: ...ut unused press any select area to display the default name then press CMD The pro grammer auto matically pro grams the name as UNUSED Serial Number Enter the eight digit serial number found on the wi...

Page 39: ...he expiration of a 10 minute Closing Check delay If the area has been disarmed outside a schedule the Closing Check delay occurs one hour after the area is disarmed At arming faulted zones are handled...

Page 40: ...Zone Types to choose from including Blank The func tional details of each response are described in Zone Type Defaults in the Appendix To change the Zone Type press any select area The display lists...

Page 41: ...the armed or disarmed condition When restored to normal no action occurs When the zone is opened from a normal disarmed state a trouble is reported When opened from a shorted armed state an alarm is r...

Page 42: ...two zones share the same transmitter the last programmed supervision time is stored as the supervision time for both zones Zero 0 indicates an unsupervised transmitter When the panel is reset the sup...

Page 43: ...o select the supervision time required for the key fob zone Press CMD to accept the default time Default is 0 Press the select area under the required number of minutes The key fob must check in at le...

Page 44: ...fore the key fob sends a message to the wireless receiver The default press time displays Press any select area to set the Button Press Time for Arm Disarm Toggle Status Output and Sensor Reset The Bu...

Page 45: ...s opened while the area is disarmed There are three actions to define Message to Transmit Output Number Output Action You must also make these selections for the Disarmed Short Armed Open and Armed Sh...

Page 46: ...one trips the total number of times as specified in Swinger Bypass Trips the panel bypasses it until the following conditions occur the area in which the zone is assigned is disarmed the zone is manua...

Page 47: ...trips while in a disarmed state The number of trips for each zone set as traffic count are added together and included with the area closing message and reported to the central station automation sys...

Page 48: ...selected the panel performs an internal reset and exits the programmer The Stop function causes the following conditions to occur All 1100INT Series DMP Wireless transmitters are reset to NORMAL The p...

Page 49: ...digits long 1 to 65535 Do not use leading zeros for the lockout code 1 Press any select area The display changes to ENTER CODE 2 Enter a 1 to 5 digit code do not enter a number higher than 65535 Press...

Page 50: ...ansmission Delay You can set Abort Reports to YES if Opening and Closing reports are not being sent If the area where the alarm occurred is disarmed during the Transmit Delay time only an Abort Report...

Page 51: ...ption Successful Display Failure Display CONNECTED CONNECT ERROR NOT ACTIVATED COMM PATH GOOD NO ACK RECEIVED Wireless Results Successful Display Failure Display LINK OK LINK ERROR DHCP OK DHCP ERROR...

Page 52: ...SSFUL displays when all Z Wave programming has been initialized Exiting the Diagnostics Menu Press CMD until STOP displays Press any select area The keypad returns to the Status List display Using the...

Page 53: ...Reset automatically occurs The System Test End message is sent to the receiver along with Verify and Fail messages for each zone under WALK test Faulted zones then display on the keypad Failed Zones...

Page 54: ...are used for reporting medical or other non panic emergencies to the central station SV Supervisory zone Used to provide 24 hour zone supervision Typical applications are high water and low and high...

Page 55: ...ripped before a message is sent Receiver Routing This selects the routing option for Auxiliary 1 or Auxiliary 2 zone types Style The abbreviations that display on the keypad for arming zone style TGL...

Page 56: ...user codes for a total of 10 000 possible combinations Access to the SPT is protected by a 4 digit service user code and a 4 digit lockout code for a total of 100 000 000 possible combinations Failure...

Page 57: ...Listed Compliance Specifications Intertek ETL Listed EN 50130 5 2011 Alarmsystems Environmentaltest methods EN 50131 1 2006 A1 2009 Alarm systems Intrusion and hold up systems System requirements EN 5...