7000INT Series Installation and Programming Guide | Digital Monitoring Products, Inc.
8
Figure 4: Access Control Wiring
Green/White*
- Connect Reader Data 0
White
- Connect Reader Data 1
Orange
- Door Strike Normally Open
Gray
- Door Strike Common
Violet
- Door Strike Normally Closed
Black
– Ground
Green
– Receive Data
Yellow
– Send Data
Red
– Keypad Power
–
Yellow & White
Zone 4
–
Orange & White
Zone 3
(REX)
–
Red & White
Zone 2
–
Brown & White
Zone 1
(7/0 Panic)
NC
C
NO
WHT
GRN
Z4 -
Z4 +
Z3 -
Z3 +
Z2 -
Z2 +
Z1 -
Z1 +
BLK
GRN
YEL
RED
External Card
Reader
To Panel Keypad Bus
1K EOL
s
s
1K EOL
s
s
1K EOL
s
s
1K EOL
s
s
*Only the green/white,
white, black, and red
wires connect to the
external card reader.