Menu 9 “CAN Bus Setup”
The SuperSigma2 controller uses our own CAN bus protocol for sending and receiving information to and from other CAN
nodes. The protocol is designed for the SuperSigma2 to act as a slave in an existing CAN environment. Detailed information
about the protocol will be provided on request. See [2] for further details.
As default the CAN system is deactivated.
Cal.
Ref.
Parameter
Calibrator
text
Options (defaults are in bold)
Default
1
CAN Node Number
CAN node
Node number
0
to 15
0
2
CAN bit rate
CANbitRt
CAN bus speed:
0 = 100kbps
1 = 125kbps
2 = 250kbps
0
3
Transmit/Receive CAN messages
Used short descriptions:
CANMsgs
0= DC & DS
1 = DC & DS & MS
2 = DC & DS & CS
3 = DC & DS & CS & MS
4= no CAN message
5= DS only
6= MS only
7= DS & MS
8= CS only
9= CS & DS
10= CS & MS
11= CS & MS &DS
(Receive &Transmit)
(Receive &Transmit)
(Receive &Transmit)
(Receive &Transmit)
(Transmit only)
(Transmit only)
(Transmit only)
(Transmit only)
(Transmit only)
(Transmit only)
(Transmit only)
4
DC : drive command
DS : drive status
MS : Motor status
CS : controller status
(receive)
(transmit)
(transmit)
(transmit)
4
Shared Line Contactor
ShareLC
0 = No shared line contactor
1 = Shared line contactor
2 = Shared line contactor CAN HMI master
3 = Shared line contactor CAN HMI slave
0
5
Last Node Sharing Line Contactor
LstNode
Node number
1
to 15
1
6
Can Control Type
(only Traction Software)
CANCtTyp
0 Speed Limit Via Can Disabled, Safe Stop 1
Disabled
;
1 Speed Limit Via Can Enabled, Safe Stop Disabled;
2 Speed Limit Via Can Disabled, Safe Stop Enabled;
3 Speed Limit Via Can Enabled, Safe Stop Enabled;
0
7
CAN motor status transmit rate
CAN_MS
100 to 1000ms
100ms
8
CAN controller status transmit rate
CAN_CS
100 to 1000ms
1000ms
9
CAN drive status transmit rate
CAN_DS
100 to 1000ms
100ms
10
CAN controller timeout timer
CAN_TO
100 to 500ms
150ms
11
CAN node ID Via digital Inputs
CAN_DIG
0 standard node ID
1 Can node identification via DigInp 1,2,3 and 5
(active only if “CANMsgs” < 4)
0
Recycle the key switch to make changes active. (Also indicated on calibrator ‘key’)