XS-110
Signal Adder Converter
Page 16 of 24 XS-110 User Manual MAN-EN-DE-XS110-01.02_13
All rights reserved to DLG Automacao Industrial
Settings
Default triggering
NPN sensor
Connect the
NEGATIVE
terminal of the sensor power supply (terminal 6) to the
last used sensor input. Hold the SET key for 5 seconds until the green LED starts
blinking.
PNP sensor
Connect the
POSITIVE
terminal of the sensor power supply (terminal 5) to the last
used sensor input. Hold the SET key for 5 seconds until the green LED starts blinking.
If the type of sensor is not set, the red LED will blink.
Ramp rise time setting
The ramp rise time is set first by setting the number of sensors to be less than 9,
then triggering the sensor input 9, connecting terminals 6 and 15 (for NPN sensors) or
terminals 5 and 15 (for PNP sensors). Using the UP and DOWN keys, adjust the required
rise time which is the time that the green LED stays lit. The minimum rise time is 0.1
seconds and the maximum is 10 seconds.
Ramp fall time setting
The ramp fall time is set first by setting the number of sensors to be less than 9,
then triggering the sensor input 10, connecting terminals 6 and 16 (for NPN sensors) or
terminals 5 and 16 (for PNP sensors). Using the UP and DOWN keys, adjust the required
fall time which is the time that the green LED stays off. The minimum fall time is 0.1
seconds and the maximum is 20 seconds.