XS-110
Signal Adder Converter
XS-110 User Manual MAN-EN-DE-XS110-01.02_13 Page 7 of 24
All rights reserved to DLG Automacao Industrial
Specification
XS-_10
/___
Enclosure:
1
Only the converter (XS-110)
6
Water-proof enclosure (XS-610)
Triggering:
/ -
Default triggering comprises only the last triggered sensor.
/ S
Sequential triggering comprises triggered sensors in pairs.
/ I
Inverted
*
default triggering comprises only the last triggered sensor.
Examples:
•
XS-110
: Default triggering Signal Adder Converter. Output changes accordingly with the
last triggered input sensor;
•
XS-110/S
: Sequential triggering Signal Adder Converter. Except the first input channel,
output changes only when input is triggered in pairs, i.e., accordingly with the last and
penultimate triggered input sensor;
•
XS-610
: Default triggering Signal Adder Converter built-in a waterproof box.
*
The operation of the inverted triggering Adder comprises similarly to the default
triggering, it differs only at the analogic output, which will change from 20 to 4 mA (when 20 mA
indicates no input sensor triggered and 4 mA indicates that all input sensors are triggered).