XS-110
Signal Adder Converter
XS-110 User Manual MAN-EN-DE-XS110-01.02_13 Page 17 of 24
All rights reserved to DLG Automacao Industrial
Sequential triggering
NPN sensor
Connect the
NEGATIVE
terminal of the sensor power supply (terminal 6) to the
last and penultimate sensor input of the sequence. Hold the SET key for 5 seconds until
the green LED starts blinking.
PNP sensor
Connect the
POSITIVE
terminal of the sensor power supply (terminal 5) to the last
and penultimate sensor input of the sequence. Hold the SET key for 5 seconds until the
green LED starts blinking.
If the type of sensor is not set, the red LED will blink.
Ramp rise time setting
The ramp rise time is set first by setting the number of sensors to be less than 9,
then triggering the sensor input 9, connecting terminals 6, 14 and 15 (for NPN sensors)
or terminals 5, 14 and 15 (for PNP sensors). Using the UP and DOWN keys, adjust the
required rise time which is the time that the green LED stays lit. The minimum rise time is
0.1 seconds and the maximum is 10 seconds.
Ramp fall time setting
The ramp fall time is set first by setting the number of sensors to be less than 9,
then triggering the sensor input 10, connecting terminals 6, 15 and 16 (for NPN sensors)
or terminals 5, 15 and 16 (for PNP sensors). Using the UP and DOWN keys, adjust the
required fall time which is the time that the green LED stays off. The minimum fall time is
0.1 seconds and the maximum is 20 seconds.