MODBUS UNIVERSAL INDICATOR
IM
–111 User manual
MAN-EN-DE-IM111-01.00_16
Page 21 of 44
All rights reserved to DLG Automação Industrial © 2011
– 2016
8.1.3 - Output menu
The IM
–111 provides an isolated analog output for input signal (process variable)
retransmission in 0-20 mA or 4-20 mA.
Retransmission is always enabled and does not require user intervention to turn it on.
Submenu
Parameter
Description
.
.
Sets the retransmission scale.
.
: 0-20 mA based on the input engineering range.
.
: 4-20 mA based on the input engineering range.
.
: 0-20 mA based on the range defined by the
.
and
.
parameters.
.
: 4-20 mA based on the range defined by the
.
and
.
parameters.
.
.
.
.
-9999 to 30000
Input retransmission lower limit.
Only used when the retransmission scale is
.
or
.
.
.
-9999 to 30000
Input retransmission upper limit.
Only used when the retransmission scale is
.
or
.
.
.
-9999 to 30000
Safe retransmission value.
The safe retransmission value is retransmitted when the input
(process variable) is out of range (burn out).
.
-100 to 100
Calibration “zero” setting.
Changes the lower calibration value. To restore factory calibration,
set this parameter to 0.
.
-100 to 100
Calibration span setting.
Changes the upper calibration value. To restore factory calibration,
set this parameter to 100.