MODBUS UNIVERSAL INDICATOR
Page 10 of 44
IM
–111 User manual
MAN-EN-DE-IM111-01.00_16
All rights reserved to DLG Automação Industrial © 2011
– 2016
**PS:
the table below specifies the minimum voltage level (square wave amplitude) required for the indicator to detect
the frequency signal properly:
Input signal (Hz)
Minimum square wave voltage
amplitude (Vdc)
1000
1.23
2000
1.24
3000
1.25
4000
1.27
5000
1.34
10000
1.80
15000
2.40
20000
3.00
25000
3.70
27700
4.00
30000
4.50
WARNING:
When using frequency signals, it is extremely important to consider proper
grounding so noise effects are minimized.
4.2 - GENERAL CHARACTERISTICS
Type
Specification
Operating temperature
0 ºC - 50 ºC
IP protection
IP
–20 rear, IP–63 frontal.
Input voltage
IM-111/AC
: 90 ~ 240 Vac, 60Hz or 100 ~ 130 Vdc
IM-111/DC
: 18 ~ 30 Vdc
Power consumption
5 VA
Construction
ABS plastic frontal, for panel mounting
Electrical connections
“Plug-in” type removable connectors
Approx. weight
0.2 kg
Dimensions
50 x 98 x 152.6 mm (height x width, depth).
Panel space required
42 × 90 mm
5 - HOW TO SPECIFY
IM-__11 /____
Finishing / Enclosure
1
Standalone universal indicator (IM-111)
6
Universal indicator installed inside a IP-65 box (IM-611)
Power
AC
90 ~ 260 Vac
DC
18 ~ 30 Vdc