IM
–111
MODBUS UNIVERSAL INDICATOR
Page 34 of 44
IM
–111 User manual
MAN-EN-DE-IM111-01.00_16
All rights reserved to DLG Automação Industrial © 2011
– 2016
Relay connections
Each relay has a NO (normally open)
and a NC (normally closed) contact.
Relay 1 uses pins 3, 4 and 5; relay 2
uses pints 13, 14 and 15. Maximum
relay load is 3 A / 220 Vac.
Auxiliary power supply
The IM
–111 provides a regulated 24
Vdc auxiliary power supply for loads
up to 50 mA.
The power supply connectors are pin
19 (+) and 20 (-).
PS.:
Available only on
IM-111/DC
.