Grid & Load connection
Only qualified AC transmission cables under the local electrical safety laws
and regulations and comply with the technical parameters of this manual
are allowed to connect to the Soluna S 8 E U - A 5 0
Recommended wire specifications for safe system operation are as shown in the
following table.
GRID side
LOAD side
6 mm² wire is recommended
6 mm² wire is recommended
Terminal crimping of wires L, N, and PE of the mains and load cables Terminal
crimping torque 3.6
–
4.6 N.m.
Note:
•
Before connecting the AC power Grid cable to the BESS , the lightning
protection and short circuit protection measures must be taken following the
local electrical safety regulations. The PE cable (grounding cable) of the system
must be reliably grounded.
•
Connect the three wires L, N, and PE of the single-phase public power Grid to
the corresponding AC terminals, fasten them, and tighten the screws. The
crimping torque is 1.5
–
2.5 N.m.
•
Connect the three wires L, N, and PE of the load to the corresponding load
terminals, fasten them, and tighten the screws. The crimping torque is 1.5
–
2.5
N.m.