Active power and reactive power setting
The Soluna BESS is capable of producing reactive power and feeding it into grid through the
setting. Feeding in management can be controlled directly by the grid company through a
dedicated communication port.
Volt-Var Response Mode
The Soluna BESS series complies with AS/NZS 4777.2: 2015 standard which introduced the
voltage-var response mode to restrict the power output of the inverter in response to the
voltage at its terminals (refer to AS/NZS 4777.2: 2015).
This mode is not enabled by default and when activated, it will sink reactive power in
response to an increasing voltage (inductive) and supply reactive power in response to a
decrease in voltage (capacitive). The voltage at which the inverter should sink/supply a
reactive power at a given % of the VA rating of the inverter can be adjusted, the default
values are given in the table below.
ALWAYS CHECK THE AS4777.2: 2015 SETTINGS WITH THE LOCAL GRID
OPERATOR
Adjusting Volt-Var mode settings
Click Q(V) icon and set V1~V4, Q1~Q4 to comply with the local Grid.
Parameters
Explanation
Default
(Reference value: Vac)
V1
Grid voltage
207
V2
Grid voltage
220
V3
Grid voltage
250
V4
Grid voltage
265
Parameters
Explanation
Default
(Reference value)
Q1
Var % rated VA
0.3
Q2
Var % rated VA
0
Q3
Var % rated VA
0
Q4
Var % rated VA
-0.3
Summary of Contents for Soluna S8 EU-A50
Page 19: ...Page 19 of 60 Appearance Figure 2 3 Appearance Number Name Remark Soluna brand LCD panel ...
Page 20: ...Page 20 of 60 ...
Page 22: ...Page 22 of 60 Installation Installation tools ...
Page 50: ...Page 50 of 60 2 Register Click Register to create new account you can use email to register ...
Page 53: ...Page 53 of 60 3 4 Now you can see your plant on the homepage ...