dIXEL

 

Installing and Operating Instructions 

1592002250

 

 

1592002250 XT151-160D GB R.1.08.03.2005 

XT151D – XT160D 

4/4 

15.

 

CONNECTIONS 

15.1

 

XT151D – 230V AC OR 120V AC OR 24V AC 

Analog

Out

Input: 4÷20mA 

0÷1V / 0÷10V 

10 11 12

PTC 

NTC

8(3)A250V

8(3)A250V

8(3)A250V

Line

Alarm

LOAD 1

LOAD 2

LOAD 3

Ho

t-K

EY

8(3)A250V

 

 

Probe: Pt100=11 - 10 (12); Thermocouple J, K, S= 11(+) - 10(-) 
115Vac supply: 1-2;  24Vac supply: 1-2 
 

15.2

 

XT160D – 230V AC OR 115V AC OR 24V AC 

 

Analog

Out

Input: 4÷20mA 

0÷1V / 0÷10V 

10 11 12

PTC 

NTC

8(3)A250V

8(3)A250V

8(3)A250V

Line

LOAD 4 LOAD 1

LOAD 2

LOAD 3

Ho

t-K

EY

8(3)A250V

 

 

Probe: Pt100=11 - 10 (12); Thermocouple J, K, S= 11(+) - 10(-) 
115Vac supply: 1-2;  24Vac supply: 1-2 

16.

 

DEFAULT SETTING VALUES 

COD Name 

Range 

°C/°F 

Lev 

Set1 

Set point1 

LS1÷US1 

0/32 

Set2 

Set point2 

LS2÷US2 

1/34 

Set3 

Set point3 

LS3÷US3 

2/36 

Set4

4

  Set point4 

LS4÷US4 

3/38 

Hy1 

Differential 1 

-Full Sc./ Full Sc. 

-1/-2  Pr1 

Hy2 

Differential 2 

-Full Sc./ Full Sc. 

-1/-2  Pr1 

Hy3 

Differential 3 

-Full Sc./ Full Sc. 

-1/-2  Pr1 

Hy4

4

 

Differential 4 

-Full Sc./ Full Sc. 

-1/-2  Pr1 

LS1 

Minimum set point1 

Down Sc./ Set1 

min 

Pr2 

LS2 

Minimum set point2 

Down Sc./ Set2 

min 

Pr2 

LS3 

Minimum set point3 

Down Sc./ Set3 

min 

Pr2 

LS4

4

 

Minimum set point4 

Down Sc./ Set4 

min 

Pr2 

US1 

Maximum set point1 

Set1/ Full Sc. 

max 

Pr2 

US2 

Maximum set point2 

Set2/ Full Sc. 

max 

Pr2 

US3 

Maximum set point3 

Set3/ Full Sc. 

max 

Pr2 

US4

4

  Maximum set point4 

Set4/ Full Sc. 

max 

Pr2 

ouC 

Output configuration 

ind= independent;  diP = dependent 

ind 

Pr2 

S1C 

Action type output 1 

in= Inverse; dir=direct 

in 

Pr2 

S2C 

Action type output 2 

in= Inverse; dir=direct 

in 

Pr2 

S3C 

Action type output 3 

in= Inverse; dir=direct 

in 

Pr2 

S4C

4

  Action type output 4 

in= Inverse; dir=direct 

in 

Pr2 

Ac 

Anti-short cycle delay: 

0÷250 sec 

Pr2 

on 

Minimum time a stage stays switched 
ON 

0÷250 sec 

Pr2 

ono 

Minimum time between 2 following 
switching ON of the same load 

0÷120 min 

Pr2 

ALC 

Alarm configuration 

rE=relat.; Ab= absolute 

rE 

Pr2 

ALL 

Minumum alarm (ALC=rE) 
                         (ALC=Ab) 

0 ÷ |Start Sc.-Set1|;  
Start Sc.÷ ALu 

10.0/ 20  Pr2 

ALU 

Maximum alarm (ALC=rE) 
                          (ALC=Ab)  

0 ÷ |Full Sc.-Set1|. 
ALL÷ Full Scale 

10.0/ 20  Pr2 

ALH 

Alarm recovery differential 

0÷Full scale 

2.0/4  Pr2 

ALd 

Alarm delay 

0÷999 min 

15 

Pr2 

dAO 

Alarm delay at start up 

0÷23h 50min 

1.3 

Pr2 

tbA

Alarm relay disabling 

no; yES 

yES 

Pr2 

AS

Alarm relay polarity 

CL÷oP 

oP 

Pr2 

So1 

Out1 status with faulty pr. 

oFF=open  on=closed 

oFF 

Pr2 

So2 

Out2 status with faulty pr. 

oFF=open  on=closed 

oFF 

Pr2 

So3 

Out3 status with faulty pr. 

oFF=open  on=closed 

oFF 

Pr2 

So4

4

 

Out4 status with faulty pr. 

oFF=open  on=closed 

oFF 

Pr2 

Lci

Start scale with current or voltage input  -1999÷1999 

various  Pr1 

Uci

2

 

End scale with current or voltage input  -1999÷1999 

various  Pr1 

OPb 

Probe calibration 

-Full Sc./ Full Sc. 

0.0 

Pr1 

rES 

Resolution 

in=NO; dE=0,1; cE=0,01 

in 

Pr2 

UdM 

Measurement unit (temp.) 
        (current/voltage

°C=°C; °F= °F; 
0=°C; 1=°F; 2=RH; 3=bar; 4=PSI, 
5=off 

various  Pr1 

PbC 

Kind of probe 

Pt=Pt100; J=tcJ; c= tck; S=tcS; 
Ptc=PTC; ntc= NTC; 0-1=0÷1V; 10= 
0÷10V; cur=0÷20mA 

various  Pr1 

P3F 

3

rd

 wire presence 

no=2 wires; yES=3 wires 

no 

Pr2 

Aoc

Analog output configuration 

Pb = probe; Er = Probe-Set1 

Pb  

Pr2 

LAo

3

  Lower An.Output limit 

Down Sc 

various  Pr2 

uAo

3

  Upper An. Output limit 

Full sc. 

various  Pr2 

SAo

3

  Analog output safety 

on; oFF 

oFF 

Pr2 

HES 

Energy saving differential 

Down Sc./ Full Sc. 

0.0 

Pr2 

i1F 

Digital input configuration 

c-H / oFF / AuS / HES / EAL / bAL  

EAL 

Pr2 

i1P 

Digital input polarity 

cL=closing; oP=opening 

cL 

Pr2 

did 

Alarm delay for dig. input 

0÷120m 

Pr2 

Adr 

Serial address 

RS485 address 

Pr2 

OnF 

oFF function enabling 

no=not enabled; oFF=enabled 

no 

Pr2 

Ptb 

Parameter table 

Readable only 

-- 

Pr2 

rEL 

Software release 

Readable only 

--- 

Pr2 

Pr2 

To access the Pr2 

Readable only 

321 

Pr1 

 

Only for XT151D;  

2

 Only for instrument with 4÷20mA or 0÷1V or 0÷10V 

3

 Only for instrument analog output 

4

 Only for XT160D 

 

Dixell S.p.A.  Z.I. Via dell’Industria, 27 
32010 Pieve d’Alpago (BL) ITALY 
tel. +39 - 0437 - 98 33  -  fax +39 - 0437 - 98 93 13 

E-mail: [email protected]  - http://www.dixell.com

 

Summary of Contents for XT151D

Page 1: ... temperature Pt Pt100 J J thermocouple c K thermocouple S S thermocouple Ptc PTC ntc ntc b Controller with current or voltage inputs cur 4 20mA 0 1 0 1V 10 0 10V 4 Push the SET key to confirm it 5 Switch the controller off and on again NOTE Before proceeding check and if necessary set with appropriate values the Minimum Set Points LS1 e LS2 and Maximum Set Points US1 e US2 See also the paragraphs ...

Page 2: ...wn Sc Set4 Sets the minimum acceptable value for the set point4 US1 Maximum set point1 Set1 Full Sc Sets the maximum acceptable value for set point1 US2 Maximum set point2 Set2 Full Sc Sets the maximum acceptable value for set point2 US3 Maximum set point3 Set3 Full Sc Sets the maximum acceptable value for set point3 US4 Maximum set point4 only for XT160D Set4 Full Sc Sets the maximum acceptable v...

Page 3: ...gain or remove the Hot key to abort the operation 11 2 HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY DOWNLOAD 1 Turn OFF the instrument 2 Insert a programmed Hot Key into the 5 PIN receptacle and then turn the Controller ON 3 Automatically the parameter list of the Hot Key is downloaded into the Controller memory the doL message is blinking followed a by flashing End 4 After 10 seconds the instrume...

Page 4: ...ation rE relat Ab absolute rE Pr2 ALL Minumum alarm ALC rE ALC Ab 0 Start Sc Set1 Start Sc ALu 10 0 20 Pr2 ALU Maximum alarm ALC rE ALC Ab 0 Full Sc Set1 ALL Full Scale 10 0 20 Pr2 ALH Alarm recovery differential 0 Full scale 2 0 4 Pr2 ALd Alarm delay 0 999 min 15 Pr2 dAO Alarm delay at start up 0 23h 50min 1 3 Pr2 tbA1 Alarm relay disabling no yES yES Pr2 AS1 Alarm relay polarity CL oP oP Pr2 So1...