dixell XT151D Installing And Operating Instructions Download Page 3

dIXEL

 

Installing and Operating Instructions 

1592002250

 

 

1592002250 XT151-160D GB R.1.08.03.2005 

XT151D – XT160D 

3/4 

P3F  Third wire presence for Pt100 probe: for using 2 or 3 wires Pt100 probes: no = 2 wires 

probe; yES = 3 wires probe. 

ANALOG OUTPUT -  OPTIONAL 

AOC Analog output configuration(only for models with analog output)  

AOC=Pb  Probe reading. The analog output parameters LAO and UAO are indipendent and 
correspond to the absolute read-out probe signal. 

 

AOC=Er Probe - Set Point1. The analog output parameters LAO and UAO are related to the 
difference between measurement of the probe and Set Point 1.  

LAO Lower analog output limit:  (only for models with analog output) minimum value of 

temperature associated to the 4mA analog output. This value can be absolute or relative to the 
Set Point 1 by setting the AOC parameter. 

UAO Upper analog output limit:  (only for models with analog output) maximum value of 

temperature associated to the 20mA  analog output. This value can be absolute or relative to 
the Set Point 1 by setting the AOC parameter. 

SAO Analog output  safety with probe fault(only for models with analog output) determines 

what state the analog output should assume when the probe is faulty: 

 

SAO = oFF; analog output = 4mA 

 

SAO = on; analog output = 20mA. 

DIGITAL INPUT 

HES Set point 1 changes during the Energy Saving cycle: (Down Sc./Full Sc.) sets the variation 

of the set point 1 during the Energy Saving cycle.  

i1F  Digital input operating mode: configure the digital input function: c-H = to invert the kind of 

action: direct - reverse; oFF  = to switch the controller off.; AUS  = Not used; HES = Energy 
Saving;  EAL = generic external alarm; bAL 

= serious external alarm: it switches 

off the loads. 

i1P  Digital input polarity: 
 

CL : the digital input is activated by closing the contact; 

 

OP : the digital input is activated by opening the contact 

did  Digital input alarm delay:  (0

÷

120 min) delay between the detection of the external alarm 

condition (i1F= EAL or i1F = bAL) and its signalling. 

OTHER 

Adr  RS485 serial address (0÷247) identifies the instrument within a control or supervising system. 
onF Swithching ON/OFF enabling  from keyboard: 
(no = disabled; yES=enabled) It permits the 

switching ON/OFF of the instrument by pressing the SET key for more than 4s. 

Ptb Parameters table: (read only) Shows the code of the parameters map. 
rEL Software release: (read only) 
Pr2  To access the Pr2 parameter programming menu. 

8.

 

INSTALLATION AND MOUNTING 

Instruments XT160D, XT151D, shall be mounted on an omega DIN rail.  
The temperature range allowed for correct operation is 0

÷

60 °C. Avoid places subject to strong 

vibrations, corrosive gases, excessive dirt or humidity. The same recommendations apply to probes. 
Let air circulate by the cooling holes. 

9.

 

ELECTRICAL CONNECTIONS 

The instruments are provided with screw terminal block to connect cables with a cross section up to 
2,5 mm

2

. Before connecting cables make sure the power supply complies with the instrument’s 

requirements. Separate the input connection cables from the power supply cables, from the outputs 
and the power connections. Do not exceed the maximum current allowed on each relay, in case of 
heavier loads use a suitable external relay. 

10.

 

SERIAL CONNECTIONS 

All models can be connected to the monitoring and supervising system XJ500 using the serial port. 
The external XJ485 serial module to interface the instrument with the monitoring and supervising 
system XJ500 is required.  
The standard ModBus RTU protocol it is used.  

 

11.

 

HOW TO USE THE HOT KEY  

11.1

 

HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD) 

1.

 

Program one controller with the front keypad. 

2.

 

When the controller is ON, insert the “Hot key” and push 

o

 key; the  "uPL"  message 

appears followed a by flashing “End” 

3.

 

Push “SET” key and the End will stop flashing. 

4.

 

Turn OFF the instrument remove the “Hot Key”, then turn it ON again. 

 
NOTE: the “Err” message is displayed for failed programming. In this case push again 

o

 key if you 

want to restart the upload again or remove the “Hot key” to abort the operation. 
 

11.2

 

HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY 

(DOWNLOAD) 

1.

 

Turn OFF the instrument. 

2.

 

Insert  a programmed “Hot Key” into the 5 PIN receptacle and then turn the Controller ON. 

3.

 

Automatically the parameter list of the “Hot Key” is downloaded into the Controller memory, 
the “doL” message is blinking followed a by flashing “End”. 

4.

 

After 10 seconds the instrument will restart working with the new parameters.  

5.

 

Remove the “Hot Key”.

 
NOTE the message “Err” is displayed for failed programming. In this case turn the unit off and then 
on if you want to restart the download again or remove the “Hot key” to abort the operation. 
 

12.

 

DIGITAL INPUT 

The controllers have 1  free contact digital input. It is programmable in 5 different configurations by 
the “i1F” parameter. 

12.1

 

INVERT THE KIND OF ACTION: HEATING-COOLING (I1F = C-H) 

This function allows to invert the regulation of the controller for both the outputs: from direct to 
inverse and viceversa. 

12.2

 

REMOTE ON/OFF (I1F = OFF) 

This function allows to switch ON and OFF the instrument. 

12.3

 

GENERIC ALARM (I1F = EAL) 

As soon as the digital input is activated the unit will wait for “did” time delay before signalling the 
EAL” alarm message. The outputs status don’t change. The alarm stops just after the digital input is 
de-activated. 

12.4

 

SERIOUS ALARM MODE (I1F = BAL) 

When the digital input is activated, the unit will wait for “did” delay before signalling the “bAL” alarm 
message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-
activated. 

12.5

 

ENERGY SAVING (I1F = HES) 

The Energy Saving function allows to change the set point1 value as the result of the SET1+ HES 
(parameter) sum. This function is enabled until the digital input is activated. 
 

13.

 

ALARM SIGNALS 

Message  Cause 

Outputs 

“PFo” 
 

Probe broken or absence  

Alarm output ON; Output 1 and 2 according 
parameters “So1” and “So2” respectively. 

“PFc”  
 

Probe short circuited 

Alarm output ON; Output 1 and 2 according 
parameters “So1” and “So2” respectively. 

“HA” 

Maximum temperature alarm 

Alarm output ON; Other outputs unchanged. 

“LA” 

Minimum temperature alarm 

Alarm output ON; Other outputs unchanged. 

“EAL” 

External alarm 

Output unchanged. 

“bAL” 

Serious external alarm 

Output OFF. 

13.1

 

ALARM RELAY STATUS 

Status of the instrument 

XT151D 

 

AS = CL 

AS= oP  

Instrument off 

13-14 open 

13-14 open 

Normal operating 

13-14 open 

13-14 closed 

Alarm present 

13-14 closed 

13-14 open 

13.2

 

SILENCING BUZZER / ALARM RELAY OUTPUT 

Once the alarm signal is detected the buzzer, if present, can be disabled by pressing any key. 
XT151D: the alarm relay status depends on the tbA parameter: with tbA=yES the relay is disabled by 
pressing any key, with tbA=no the alarm relay remains enabled as long as the alarm lasts. The 
display signal remains as long as the alarm condition remains.  

13.3

 

ALARM RECOVERY  

Probe alarms “PFo”, “PFc” start few seconds after the fault in the probe; they automatically stop few 
seconds after the probe restarts normal operation. Check connections before replacing the probe. 
Max. and min. alarms “HA” and “LA” automatically stop as soon as the variable returns to normal 
values. 
Alarms “bAL” and “EAL” recover as soon as the digital input is disabled. 

14.

 

TECHNICAL DATA 

Housing: self extinguishing ABS. 
Case:XT160D, XT151D
: 4 DIN modules 70x85 mm; depth 61mm. 
Mounting: XT160D, XT151D: DIN RAIL 
Protection: IP20. 
Connections: 
Screw terminal block 

 2,5 mm

2

 heat-resistant wiring. 

Power supply: 24Vac 

±

 10%; or 230Vac 

±

 10%, 50/60Hz or 110Vac, 

±

 10%, 50/60Hz 

Power absorption: 3VA max. 
Display: 3 ½ digits, red LED 
Inputs: according to the order: NTC/PTC or NTC/PTC /Pt100 /Thermocouple J, K, S or 4÷20mA/ 

0÷1V / 0÷10V 

Relay outputs: 

Output1: relay 8(3)A, 250Vac 
Output2: relay 8(3)A, 250Vac 
Output3: relay 8(3)A, 250Vac 
Output4 (XT160D): relay 8(3)A, 250Vac 
Alarm: (XT151D), 8(3)A, 250Vac  

Other output: buzzer (optional) 
Kind of action: 
1B.; Pollution grade: normal;  
Software class: A.; Data storing: on the non-volatile memory (EEPROM). 
Operating temperature: 0÷60 °C (32÷140°F); Storage temperature: -30÷85 °C  (-22÷185°F).  
Relative humidity: 20

÷

85% (no condensing) 

Measuring and regulation range: according to the probe 
Controller Accuracy a 25°C: better than 

±

0,5% of full scale 

Summary of Contents for XT151D

Page 1: ... temperature Pt Pt100 J J thermocouple c K thermocouple S S thermocouple Ptc PTC ntc ntc b Controller with current or voltage inputs cur 4 20mA 0 1 0 1V 10 0 10V 4 Push the SET key to confirm it 5 Switch the controller off and on again NOTE Before proceeding check and if necessary set with appropriate values the Minimum Set Points LS1 e LS2 and Maximum Set Points US1 e US2 See also the paragraphs ...

Page 2: ...wn Sc Set4 Sets the minimum acceptable value for the set point4 US1 Maximum set point1 Set1 Full Sc Sets the maximum acceptable value for set point1 US2 Maximum set point2 Set2 Full Sc Sets the maximum acceptable value for set point2 US3 Maximum set point3 Set3 Full Sc Sets the maximum acceptable value for set point3 US4 Maximum set point4 only for XT160D Set4 Full Sc Sets the maximum acceptable v...

Page 3: ...gain or remove the Hot key to abort the operation 11 2 HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY DOWNLOAD 1 Turn OFF the instrument 2 Insert a programmed Hot Key into the 5 PIN receptacle and then turn the Controller ON 3 Automatically the parameter list of the Hot Key is downloaded into the Controller memory the doL message is blinking followed a by flashing End 4 After 10 seconds the instrume...

Page 4: ...ation rE relat Ab absolute rE Pr2 ALL Minumum alarm ALC rE ALC Ab 0 Start Sc Set1 Start Sc ALu 10 0 20 Pr2 ALU Maximum alarm ALC rE ALC Ab 0 Full Sc Set1 ALL Full Scale 10 0 20 Pr2 ALH Alarm recovery differential 0 Full scale 2 0 4 Pr2 ALd Alarm delay 0 999 min 15 Pr2 dAO Alarm delay at start up 0 23h 50min 1 3 Pr2 tbA1 Alarm relay disabling no yES yES Pr2 AS1 Alarm relay polarity CL oP oP Pr2 So1...

Reviews: