Operating instructions
cod. 1592011000
1592011000 XC706M GB 31-08-2001
rel. 1.0
Pa. 15 / 23
Regulation according to the running hours
The algorithm switch on and off the loads according to the running hours of each load. In this
way the running hours are balanced.
Example
Cpnu = 4
number of compressors
CtyP = 1 homogeneous
compressors.
CPSt = 1
one step for each compressors.
rty = Pb
proportional band regulation
Sty = rot
fixed sequence
FdLy = 0
“don” delay at first call not enabled.
dLF= 0
“doF” delay at first call not enabled.
&
&
&
&
6(7
6HW3EG
6HW3EG
=,&
6HW3EG
6HW3EG
GRQ
GR)
$// /2$'6 21
$// /2$'6 2))
This draw highlights the doF time: the loads are in fact turned off only when the doF time is
over.
7. Mounting & installation
The instruments are suitable only for internal use. They are panel mounted, hole dims 135x69
mm, and fixed with the supplied clips.
The ambient operating temperature range is between 0÷55°C.
Avoid locations subject to heavy vibration, corrosive gases or excessive dirt. The same applies
to the probes. Ensure ventilation around the instrument.