                           XW272K

 

2/5 

 

4.5

 

HOW TO SEE AND MODIFY THE SET POINT 

 
 

 

1.  Push and immediately release the 

SET key: the display will show the Set point value; 

2.  The SET LED start blinking; 
3.  To change the Set value push the 

è 

or 

à

 arrows within 10s. 

4.  To memorise the new set point value push the 

SET key again or wait 10s. 

4.6

 

TO START A MANUAL DEFROST  

 

 

 
1.  Push the 

DEF key for more than 2 seconds and a manual defrost will start. 

4.7

 

TO ENTER IN PARAMETERS LIST “PR1”  

 
To enter the parameter list “Pr1” (user accessible parameters) operate as follows: 
 

 

 
1.  Enter the Programming mode by pressing the Set and DOWN key 

for few seconds (

 and 

 start blinking). 

2.  The instrument will show the first parameter present in “Pr1” 

 
 
 
 

4.8

 

TO ENTER IN PARAMETERS LIST “PR2” 

 
To access parameters in “

Pr2”: 

1.

 

Enter the “Pr1” level. 

2.

 

Select “Pr2” parameter and press the “

SET” key.  

3.

 

The “PAS” flashing message is displayed, shortly followed by “0 - -” with a flashing zero. 

4.

 

Use 

è

 or 

à

 to input the security code in the flashing digit; confirm the figure by pressing “

SET”. The 

security code is “321“. 

5.

 

If the security code is correct the access to “Pr2” is enabled by pressing “

SET” on the last digit. 

 
Another possibility is the following: after switching ON the instrument the user can push Set and DOWN keys 
within 30 seconds. 
 
NOTE: each parameter in “Pr2” can be removed or put into “Pr1” (user level) by pressing “SET” + 

à

. When 

a parameter is present in “Pr1” LED 

 is on. 

4.9

 

HOW TO CHANGE THE PARAMETER VALUE 

 
1.

 

Enter the Programming mode. 

2.

 

Select the required parameter with 

è

 or 

à

3.

 

Press the “

SET” key to display its value (

 and 

 LED starts blinking). 

4.

 

Use 

è

 or 

à

 to change its value. 

5.

 

Press “

SET” to store the new value and move to the following parameter. 

To exit: Press SET + UP or wait 15s without pressing a key. 

NOTE: the new programming is stored even when the procedure is exited by waiting the time-out. 

4.10

 

HOW TO LOCK THE KEYBOARD 

 
 

 

 

1.

  

Keep the 

è

 and 

à

 keys pressed together for more than 3 s the 

è

 and 

à

 keys. 

2. 

 

The “POF” message will be displayed and the keyboard is locked. At this point it is 
only possible the viewing of the set point or the MAX o Min temperature stored and 
to switch ON and OFF the light, the auxiliary output and the instrument. 

 

TO UNLOCK THE KEYBOARD 

 
Keep the 

è

 and 

à

 keys pressed together for more than 3s. 

 

4.11

 

ON/OFF FUNCTION 

 
 

 

By pushing the 

ON/OFF key, the instrument shows “OFF” for 5 sec. and the ON/OFF LED 

is switched ON. 
During the OFF status, all the relays are switched OFF and the regulations are stopped; if 
a monitoring system is connected, it does not record the instrument data and alarms. 

N.B. During the OFF status the Light and AUX buttons are active.  

4.12

 

TO SEE THE PROBE VALUES 

 
1.

 

Enter in “

Pr2” level. 

2.

 

Select “

Prd” parameter with 

è

 or 

à

3.

 

Press the “

SET” key to display “Pb1” label alternate with Pb1 value. 

4.

 

Use 

è 

and 

à

 keys to display the other probe values.  

5.

 

Press “

SET” to move to the following parameter. 

 

5.

 

PARAMETER LIST 

 
REGULATION 
 

Hy Differential: 

(0,1÷25,5°C; 1÷45°F): Intervention differential for set point, always positive. Compressor 

Cut IN is Set Point Plus Differential (Hy). Compressor Cut OUT is when the temperature reaches the 
set point. 

LS  Minimum set point limit: (-50,0°C

÷

SET; -58°F÷SET) Sets the minimum acceptable value for the set 

point. 

US  Maximum set point limit: (SET

÷

110°C; SET÷230°F) Set the maximum acceptable value for set 

point. 

OdS  Outputs activation delay at start up: (0÷255 min) This function is enabled at the initial start up of the 

instrument and inhibits any output activation for the period of time set in the parameter. (AUX and Light 
can work) 

CCO  Compressors configuration : (Se,Al)  

Se : The first compressor is always switched on before the second one. 

Al : The compressors are switched on in an alternate way. 

AC  Anti-short cycle delay: (0÷30 min) interval between the compressor stop and the following restart. 

AC1  Time delay between turning on compressor 1 and 2 : (0÷255 sec) allows to set the delay between 

turning on the first and the second compressor. 

CCt Thermostat override: (0min ÷23h 50min) allows to set the length of the continuous cycle. Can be 

used, for instance, when the room is filled with new products.

 

Con Compressor ON time with faulty probe: (0÷255 min) time during which the compressor is active in 

case of faulty thermostat probe. With COn=0 compressor is always OFF. 

COF Compressor OFF time with faulty probe: (0÷255 min) time during which the compressor is off in 

case of faulty thermostat probe. With COF=0 compressor is always active. 

 
DISPLAY 
 

CF  Temperature measurement unit: °C = Celsius; °F = Fahrenheit . When the measurement unit is 

changed the SET point and the values  of the regulation parameters have to be modified

 

rES  Resolution (for °C): (in = 1°C; de = 0,1°C) allows decimal point display. 

de = 0,1°C; in = 1 °C  

Red  Remote display : select which probe is displayed by the remote display (T620)  

P1 = Thermostat probe; P2 = Evaporator probe; P3 = auxiliary probe;  

1r2 = difference between P1 and P2 (P1-P2) 

 
DEFROST 
 

tdF   Defrost type:  

rE = electrical heater (Compressor OFF) 

rT = thermostat defrost. During the defrost time “MdF”, the heater switches On and OFF depending on 

the evaporator temperature and “dtE” value. 

in = hot gas (Compressor and defrost relays ON) 

EdF Defrost mode:  

 

in = interval mode. The defrost starts when the time “Idf” is expired. 

Sd = Smartfrost mode. The time IdF (interval between defrosts) is increased only when the 

compressor is running (even non consecutively) and only if the evaporator temperature is less than the 
value in "

SdF” (set point for SMARTFROST).  

SdF  Set point for SMARTFROST: (-30

÷

30 °C/ -22

÷

86 °F) evaporator temperature which allows the IdF 

counting (interval between defrosts) in SMARTFROST mode. 

 dtE   Defrost termination temperature: (-50,0÷110,0°C; -58÷230°F) (Enabled only when the evaporator 

probe is present) sets the temperature measured by the evaporator probe which causes the end of 
defrost. 

IdF Interval between defrosts: (1÷120h) Determines the time interval between the beginning of two 

defrost cycles. 

MdF  (Maximum) duration of defrost: (0÷255 min) When P2P = n, no evaporator probe, it sets the defrost 

duration, when 

P2P = y, defrost end based on temperature, it sets the maximum length for defrost. 

dFd   Display during defrost:  

 rt = real temperature; it = temperature reading at the defrost start; Set = set point; dEF = “dEF” label; 

dEG = “dEG” label; 

dAd  Defrost display time out: (0

÷

255 min) Sets the maximum time between the end of defrost and the 

restarting of the real room temperature display. 

Fdt Drain down time: (0÷60 min.) time interval between reaching defrost termination temperature and the 

restoring of the control’s normal operation. This time allows the evaporator to eliminate water drops 
that might have formed due to defrost.

 

dPO First defrost after start-up:   

 y 

= Immediately; 

n = after the IdF time 

dAF  Defrost delay after fast freezing: (0min÷23h 50min)  after a Fast Freezing cycle, the first defrost will 

be delayed for this time. 

 
FANS 
 

FnC  Fan operating mode: 

C-n = running with the compressor, OFF during the defrost;  

C-y = running with the compressor, ON during the defrost; 

O-n = continuous mode, OFF during the defrost; 

O-y = continuous mode, ON during the defrost; 

Fnd Fan delay after defrost: (0÷255 min) The time interval between the defrost end and evaporator fans 

start.

 

FSt Fan stop temperature: (-50÷110°C; -58÷230°F) setting of temperature, detected by evaporator 

probe, above which the fan is always OFF. 

 

 

ALARMS 
 

ALC  Temperature alarm configuration 

rE = High and Low alarms related to Set Point  

Ab = High and low alarms related to the absolute temperature. 

ALU  High temperature alarm setting:  

 

ALC= rE, 0 

÷

 50°C or 90°F 

 

ALC= Ab, ALL 

÷

 110°C or 230°F 

 

when this temperature is reached and after the ALd delay time the HA alarm is enabled. 

 

ALL  Low temperature alarm setting: 

 

ALC = rE , 0 

÷

 50 °C or 90°F 

 

ALC = Ab , - 50°C or -58°F 

÷

 ALU 

 

when this temperature is reached and after the ALd delay time, the LA alarm is enabled,. 

AFH Temperature alarm and fan differential: (0,1÷25,5°C; 1÷45°F) Intervention differential for 

temperature alarm set point and fan regulation set point, always positive.

 

ALd Temperature alarm delay: (0÷255 min) time interval between the detection of an alarm condition and 

the corresponding alarm signalling. 

dAO Delay of temperature alarm at start-up: (0min÷23h 50min) time interval between the detection of the 

temperature alarm condition after the instrument power on and the alarm signalling.

 

EdA  Alarm delay at the end of defrost: (0

÷

255 min) Time interval between the detection of the 

temperature alarm condition at the end of defrost and the alarm signalling. 

dot   Delay of temperature alarm after closing the door : (0

÷

255 min) Time delay to signal the 

temperature alarm condition after closing the door. 

doA   Open door alarm delay:(0÷254min,nu) delay between the detection of the open door condition and its 

alarm signalling: the flashing message “

dA” is displayed. If doA=nu the door alarm will be not 

signalled. 

nPS   Pressure  switch  number: (0 

÷

15) Number of activation of the pressure switch, during the “

did” 

interval, before signalling the alarm event (I2F= PAL). 

 
ANALOGUE OUTPUT 4÷20 mA (OPTIONAL) 

Reviews: