Dixell

 

Installing and Operating Instructions 

rel.1.0 –25/10/2000 - cod. 1592009540 

 

1592009540 XW272K_full GB 

                           XW272K

 

3/5 

 

 

AOS Analogue output start point: (-50÷110°C or -58°÷230°F). Sets the temperature at which the 

analogue output begins. 

APB  Analogue output band width: (-50÷110°C or -58°÷230°F) sets the width of the regulation band for 

the analogue output. If APb is 

positive then it is above the start point and the kind of action is direct 

(condenser application). If APb is 

negative then it is below the start point and the kind of action is 

inverse (evaporator application).  

CAO  Input type for the analogue output: four input types can be selected: 

P1=room probe temperature; P2 = evaporator probe temperature; P3=temperature of the third probe; 

1r2= temperature difference between the room probe and the evaporator probe 

 

 

PROBE INPUTS 
 

Ot  Thermostat probe calibration: (-12.0

÷

12.0°C/ -21

÷

21°F) allows to adjust possible offset of the 

thermostat probe. 

OE    Evaporator  probe  calibration:  (-12.0

÷

12.0°C/ -21

÷

21°F) allows to adjust possible offsets of the 

evaporator probe. 

O3  Auxiliary probe calibration: (-12.0

÷

12.0°C/ -21

÷

21°F) allows to adjust possible offsets of the 

evaporator probe. 

P2P  Evaporator probe presence:  

n= not present: the defrost stops only by time; y= present: the defrost stops by temperature and time. 

P3P  Auxiliary probe presence: n= not present; y= present. 

HES  Temperature increase during the Energy Saving cycle : (-30,0°C 

÷

 30,0°C / -22÷86°F) sets the 

increasing value of the set point during the Energy Saving cycle.  

  

 

DIGITAL INPUTS 
 

odc  Compressor and fan status when open door:  

no = normal; Fan = Fan OFF; CPr = Compressor OFF; F_C = Compressor and fan OFF.  

I1P  Door switch input polarity: 

 

CL : the digital input is activated by closing the contact; 

 

OP : the digital input is activated by opening the contact. 

I2P  Configurable digital input polarity: 

 

CL : the digital input is activated by closing the contact; 

 

OP : the digital input is activated by opening the contact 

 

 

 

I2F  Digital input operating mode: configure the digital input function: 

 EAL 

= generic alarm; 

bAL = serious alarm mode; PAL = Pressure switch; 

   

dFr = Start defrost; AUS = Not used; Es = Energy Saving; onF = remote On/OFF.  

did   Time interval/delay for digital input alarm:(0

÷

255 min.) Time interval to calculate the number of the 

pressure switch activation when I2F=PAL. If I2F=EAL or bAL (external alarms), “did” parameter defines 
the time delay between the detection and the successive signalling of the alarm. 

 
OTHER 
 

Adr   RS485  serial  address  (1÷247):  Identifies the instrument address when connected to a ModBUS 

compatible monitoring system. 

Rel   Release software: (read only) Software version of the microprocessor. 

Ptb   Parameter table: (read only) it shows the original code of the 

dIXEL

 parameter map. 

Prd    Probes  display:  (read only) display the temperature values of the evaporator probe Pb2 and the 

auxiliary probe Pb3. 

Pr2   Access to the protected parameter list (read only). 

 

6.

 

DIGITAL INPUTS 

 
The Wing series can support up to 2 free contact digital inputs. One is always configured as door switch, the 
second is programmable in seven different configurations by the “

I2F” parameter. 

 

6.1

 

DOOR SWITCH INPUT  

 
It signals the door status and the corresponding relay output status through the “

odc” parameter: 

no = normal (any change); 

Fan = Fan OFF; 

CPr = Compressor OFF; 

F_C = Compressor and fan OFF. 

 

Since the door is opened, after the delay time set through parameter “

dOA”, the alarm output is enabled and 

the display shows the message “

dA”. The alarm stops as soon as the external digital input is disabled again. 

During this time and then for the delay “

dot” after closing the door, the high and low temperature alarms are 

disabled. 

6.2

 

CONFIGURABLE INPUT - GENERIC ALARM (EAL) 

 
As soon as the digital input is activated the unit will wait for “

did” time delay before signalling the “EAL” alarm 

message. The outputs status don’t change. The alarm stops just after the digital input is de-activated. 

6.3

 

CONFIGURABLE INPUT - SERIOUS ALARM MODE (BAL) 

 
When the digital input is activated, the unit will wait for “

did” delay before signalling the “BAL” alarm 

message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-
activated. 

6.4

 

CONFIGURABLE INPUT - PRESSURE SWITCH (PAL) 

 
If during the interval time set by “

did” parameter, the pressure switch has reached the number of activation of  

the “

nPS” parameter, the “PAL” pressure alarm message will be displayed. The compressor and the 

regulation are stopped. When the digital input is ON the compressor is always OFF. 

6.5

 

CONFIGURABLE INPUT - START DEFROST (DFR) 

 
It executes a defrost if there are the right conditions. After the defrost is finished, the normal regulation will 
restart only if the digital input is disabled otherwise the instrument will wait until the “Mdf” safety time is 
expired. 

6.6

 

CONFIGURABLE INPUT - ENERGY SAVING (ES) 

 

The Energy Saving function allows to change the set point value as the result of the SET+ HES (parmeter) 
sum. This function is enabled until the digital input is activated. 

6.7

 

CONFIGURABLE INPUT -  REMOTE ON/OFF (ONF) 

 
This function allows to switch ON and OFF the instrument. 

6.8

 

DIGITAL INPUTS POLARITY  

 
The digital inputs polarity depends on “

I1P” and “I2P” parameters. 

 CL : the digital input is activated by closing the contact. 

 OP : the digital input is activated by opening the contact 

 

7.

 

ANALOGUE OUTPUT 4÷20 mA (OPTIONAL) 

 
The analogue output is obtained through a 4

÷

20mA signal proportional to the input selected in parameter 

CAO”. Through the analogue output the speed of fans can be regulated according to the input variable. 

The following input types can be selected through the “

CAO” parameter: 

 

CAO” = P1 room 

temperature 

 

CAO” = P2 evaporator 

temperature 

 

CAO” = P3  third probe temperature 

 

CAO” = 1r2  room temperature - evaporator temperature 

 
To adjust the analogue output the following parameters are available: 

AOS” = Start point for analogue output  

APb” = Band width for analogue output can be either positive (direct action) and negative  

(inverse action). 

 
 

Named T the input, the relationship input-output is given by the following charts  
 
 
 

   

 

 

 
 
 

 

 

 

NOTE: When the defrost is in progress, the analogue output is set to the minimum value (4 mA). This 

condition lasts until the defrost terminates. 
 

8.

 

INSTALLATION AND MOUNTING 

 

T620 keyboard shall be mounted on vertical panel, in a 150x31 mm hole, and fixed using two screws 

 3 x 

2mm. To obtain an IP65 protection grade use the front panel rubber gasket (mod. RG-L). Power module 

XW272K shall be mounted in a panel with two or more screws and it must be connected to the keyboard by 
means of a two-wire cable (

 1mm). The temperature range allowed for correct operation is 0 - 60 °C. Avoid 

places subject to strong vibrations, corrosive gases, excessive dirt or humidity. The same recommendations 
apply to probes. Let the air circulate by the cooling holes. 
 

 

8.1

 

T620 CUT OUT 

 
 
 
 

165

150

31

+0.5

-0

+0

.5 -0

+1

-1

Ø3 x2

 

 

 

8.2

 

MOUNTING WITH KEYBOARD COVER OPENING DOWNWARD 

 
 
 