Dixell

 

Installing and Operating Instructions 

rel.1.0 –25/10/2000 - cod. 1592009540 

 

1592009540 XW272K_full GB 

                           XW272K

 

5/5 

 

 

14.

 

CONNECTIONS 

14.1

 

XW272K 

 
 

 

 

 

 

 

 

Connector number 

Description 

Connector number  Description 

HOT KEY 

Hot key for programming 

9 - 10 

Door switch 

RS485 (Optional) 

RS485 direct output 

11 - 12 

Alarm relay  

An.Out (Optional) 

4÷20 mA analogue output 

13 - 14 

Compressor relay 

KEY (+) 

+ :connection for keyboard 

15 

Phase 

KEY (-) 

- : connection for keyboard 

16 

Neutral 

1 – 2 

Display probe 

17 - 18 

Light relay 

3 – 4 

Defrost probe 

19 - 20 

Defrost relay 

5 – 6 

Room probe 

21 - 22 

Fan relay  

7 – 8 

Configurable digital input  

18 -19 

2

nd

 compressor relay 

 

 

 
 

 

 

 

 

 

 

 
 

 

 

 

 

 

 

15.

 

DEFAULT SETTING VALUES 

 

Label 

Name 

  Range 

Default 

Level 

 

REGULATION  

°C/°F 

XW272K 

Set Set 

point 

LS÷US 

-5/23 

Pr1 

Hy 

Differential 

0,1÷25,5 °C  

1÷45°F 

2/4 Pr1 

LS 

Minimum set point 

 -50,0°C÷SET 

-58°F÷SET 

-30/-22 Pr2 

US 

Maximum set point 

SET ÷ 110°C  

SET ÷ 230°F 

20/68 Pr2 

OdS 

Outputs activation delay at start up 

0÷255 min. 

Pr2 

CCO 

Compressors configuration 

Se, Al 

Se 

Pr2 

AC 

Anti-short cycle delay 

0÷30 min. 

Pr1 

AC1  

Delay between turning ON 

0÷255 sec. 

10 

Pr2 

CCt 

Compressor ON time during fast freezing 

0 ÷ 23h 50 min. 

Pr2 

COn 

Compressor ON time with faulty probe 

0÷255 min. 

15 

Pr2 

COF 

Compressor OFF time with faulty probe 

0÷255 min. 

30 

Pr2 

 DISPLAY 

 

 

 

CF Temperature 

 

measurement unit 

°C ÷ °F 

°C 

Pr2 

rES Resolution 

 

(integer/decimal point) 

in ÷ de 

de 

Pr1 

Red 

Remote display  

P1 ÷ 1r2 

P1 

Pr2 

 DEFROST 

 

 

 

tdF 

Defrost type 

rE,  rT,  in  

RE 

Pr1 

EdF 

Defrost mode 

In, Sd 

In 

Pr2 

SdF 

Set point for SMART DEFROST 

-30 ÷ +30°C  

-22÷+86°F 

0/32 Pr2 

Label 

Name 

  Range 

Default 

Level 

dtE 

Defrost termination temp. 
(1°Evaporator) 

-50,0÷110°C 

 -58÷230°F 

8/46 Pr1 

IdF 

Interval between defrost cycles 

1÷120h 

Pr1 

MdF 

(Maximum) length for 1° defrost 

0÷255 min. 

30 

Pr1 

dFd 

Displaying during defrost 

rt, it, SEt, 

dEF, dEG 

It Pr2 

dAd 

MAX display delay after defrost 

0÷255 min. 

30 

Pr2 

Fdt 

Draining time 

0÷60 min. 

Pr2 

dPO 

First defrost after start up 

n ÷ y 

Pr2 

dAF 

Defrost delay after fast freezing 

0 ÷ 23h 50 min. 

Pr2 

 FANS 

 

 

 

FnC 

Fans operating mode 

C-n, C-y, 

O-n, O-y  

O-n Pr2 

Fnd 

Fans delay after defrost 

0÷255 min. 

10 

Pr2 

FSt 

Fans stop temperature 

-50,0÷110°C 

-58÷230°F 

2/35 Pr2 

 ALARMS 

 

 

 

ALC 

Temperature alarms configuration 

rE÷Ab 

rE 

Pr2 

ALU 

MAXIMUM temperature alarm 

-50,0÷110°C  

-58÷230°F 

10/20 Pr1 

ALL 

minimum temperature alarm 

-50,0÷110°C 

 -58÷230°F 

10/20 Pr1 

AFH 

Temperature alarm and fan differential 

0,1÷25,5 °C 

 1÷45°F 

2/4  

ALd 

Temperature alarm delay 

0÷255 min. 

15 

Pr2 

dAO 

Delay of temperature alarm at start up 

0 ÷ 23h 50 min. 

1,3 

Pr2 

EdA 

Alarm delay at the end of defrost  

0÷255 min. 

30 

Pr2 

dot 

Delay of temperature alarm after closing the door   0÷255 min. 

15 

Pr2 

dOA 

Open door alarm delay  

0÷254 min.,nu 

15 

Pr2 

nPS 

Pressure switch activation number 

0÷15 

Pr2 

 

ANALOGUE OUTPUT 4÷20mA (Optional) 

 

 

 

AOS 

Analogue output start point 

-50,0÷110°C  

-58÷230°F 

32 

Pr2 

APb 

Analogue output band width 

-50,0÷110°C  

-58÷230°F 

0 Pr2 

CAO 

Input type for the analogue output 

P1÷1r2 

P1 

Pr2 

 ANALOGUE 

INPUTS 

 

 

 

Ot 

Thermostat probe calibration 

-12,0÷12,0°C  

 -21÷21°F 

0 Pr1 

OE 

Evaporator probe calibration 

-12,0÷12,0°C / -

21÷21°F 

0 Pr2 

O3 

Auxiliary probe calibration 

-12,0÷12,0°C  

 -21÷21°F 

0 Pr2 

P2P 

Evaporator probe presence 

n ÷ y 

Pr2 

P3P 

Auxiliary probe presence 

n ÷ y 

Pr2 

HES 

Temperature increase during the Energy Saving 
cycle  

-30÷30°C  

-22÷86°F 

0 Pr2 

 

DIGITAL INPUTS 

 

 

 

Odc 

Open door control  

No, Fan,  

CPr, F_C 

Fan Pr2 

I1P Door 

switch 

polarity 

CL÷OP 

CL 

Pr2 

I2P 

Configurable digital input polarity 

CL÷OP 

CL 

Pr2 

i2F 

Digital input configuration 

EAL, bAL, PAL,  

dFr, AUS, ES, 

OnF 

EAL Pr2 

dId 

Digital input alarm delay 

0÷255 min. 

Pr2 

 

OTHER  

 

 

Adr Serial 

address 

0÷247 

Pr1 

rEL 

Software release 

- - - 

1.0 

Pr2 

Ptb 

Map code 

- - - 

- - - 

Pr2 

Prd 

Probes display 

Pb1÷Pb3 

- - - 

Pr2 

Pr2 

Access parameter list 

- - - 

- - - 

Pr2 

 

 

 
 

 

 
 

 
 

 

 
 

 

 
 

 
 

 

 
 

 

 
 

 

 
 

 
 

 

 
 

 

 
 

 
 

 

 
 

 

 
 

 
 

 

 
 

 

 
 

Dixell s.r.l. Via dell’Industria, 27 - 32010 Z.I Pieve d’Alpago (BL) ITALY  