IC100C Series
PRELIMINARY
1592015000 Manual IC100C Series 28/05/03 Page 38 di 38
38.
T
ECHNICAL
D
ATA
Housing:
Self extinguishing ABS.
Case:
Front panel 32x74 mm, depth 60mm (“C” format);
Front panel 38x185 mm; depth 75mm (“L” format)
Mounting :
“C” format panel mounting in a 29x71 mm panel cut-out
“L” format panel mounting in a 150x31 mm panel cut-out with two
screws.
∅
3 x 2mm. Distance between the holes 165mm
Protection:
IP65.
Frontal protection:
IP65 with frontal gasket mod RG-L or C model.
Connections:
Removable terminal block 12 and 14 ways;
Power supply:
12Vac/dc
±
10%, 24Vac/dc
±
10%, 50-60Hz.
Power absorption:
5VA max.
Display:
3 digits red led and 4 digit orange led.
Inputs:
4 NTC probes,or 3 NTC probes and one 4..20mA.
Digital inputs
: 5 free voltage
Relay outputs: 5
relay SPDT 8(3)A, 250Vac
Open collector:
alarm output: 12V, 40mA.
Analogue output:
4..20mA for fan control, trigger for fan control
Serial output :
TTL standard
Communication protocol:
Modbus – RTU
Data storing:
on the non-volatile memory (EEPROM).
Kind of action:
1B.
Pollution grade:
normal
Software class:
A.
Operating temperature:
0÷60 °C.
Storage temperature:
-25÷60 °C.
Relative humidity:
20
÷
85% (no condensing)
Measuring range: NTC probe:
-40÷110°C.
Resolution:
0,1 °C or 1°C.
Accuracy (ambient temp. 25°C)
: ±0,5 °C ±1 digit
Dixell
s.r.l. Z.I. Via dell’Industria, 27
32010 Pieve d’Alpago (BL) ITALY
tel. +39 - 0437 - 98 33 - fax +39 - 0437 - 98 93 13
E-mail:[email protected] - http://www.dixell.com