IC100C Series
PRELIMINARY
1592015000 Manual IC100C Series 28/05/03 Page 17 di 38
34.
O
UTPUT
L
OCK FOR
A
LARM
E
VENT
T
ABLE
Alarm
Code
Alarm Description
Comp.
1
Comp.
2
Anti - freeze
Heater
Water
Pump
Supply
air fan
Cond.
fan
P1
Pb1 Probe Alarm
Yes
Yes
Yes
with Ar19 =0
Yes
P2
Pb2 Probe Alarm
Yes
Yes
Yes
with Ar19 =0
Yes
P3
Pb3 Probe Alarm
Yes
Yes
Yes
with Ar19 =0
Yes
P4
Pb4 Probe Alarm
Yes
Yes
Yes
with Ar19 =0
Yes
A01
High pressure alarm from digital
input
Yes
Yes
A02
Low pressure alarm from digital
input
Yes
Yes
Yes
A03
Low temperature alarm of supplied air
A04
Low temperature outlet air
Yes
Yes
Yes
Yes
A05
High temperature / high pressure
alarm
Yes
Yes
A06
Low temperature / low pressure
alarm
Yes
Yes
Yes
A07
Anti freezer digital input
Yes
Yes
Yes
A07
Anti-freeze digital input alarm
Yes
Yes
Yes
A07
Anti-freeze alarm motocondensing unit
Yes
Yes
Yes
Yes
A08
Water flow Alarm
Yes
Yes
Heater - boiler
Yes
Yes
A08
Supply air fan thermal protection CF01= 0,1 Yes
Yes
Integration
heater Yes
Yes
A09
Compressor 1 thermal protection
Yes
A10
Compressor 2 thermal protection
Yes
A11
Condenser fan thermal protection
Yes
Yes
Yes
A12
Defrost
error
A13
Compressor 1 maintenance
A14
Compressor 2 maintenance
A15
Water pump / supply air fan maintenance
rtC
Clock
alarm
rtF
Clock
alarm
EE
Eeprom
error
Yes
Yes
Yes
Yes Yes Yes
ACF1
Configuration alarm
Yes
Yes
Yes
Yes Yes Yes
ACF2
Configuration alarm
Yes
Yes
Yes
Yes Yes Yes
ACF3
Configuration alarm
Yes
Yes
Yes
Yes Yes Yes
ACF4
Configuration alarm
Yes
Yes
Yes
Yes Yes Yes
ACF5
Configuration alarm
Yes
Yes
Yes
Yes Yes Yes
FErr
Functioning error (motocond. )
Yes
Yes
Yes
Yes
Yes
AFr
Frequency
alarm
Yes
Yes
Yes
Yes Yes Yes