IC100C Series
PRELIMINARY
1592015000 Manual IC100C Series 28/05/03 Page 21 di 38
CF36
Default read-out of the display.
0 = Pb1 on the upper side, Pb3 or Pb4 on the lower
side.
1 = Pb2 on the upper side, Pb3 or Pb4 on the lower
side.
2 = Pb1 on the upper side, the clock on the lower
side.
3 = Pb2 on the upper side, the clock on the lower
side.
CF37
Firmware release identification.
CF38
Eeprom parameter map identification.
Pr2
Password value from 0 to 999.
36.3
Dynamic Setpoint Parameters
Sd01
Dynamic Setpoint configuration.
0 = Function enabled;
1 = Function disabled.
Sd02
It determines the maximum offset of the setpoint
value reachable in Chiller mode.
Sd03
It determines the maximum offset of the setpoint
value reachable in Heat Pump mode.
Sd04
External air temperature setpoint in Chiller
mode.
Sd05
External air temperature setpoint in H.P. mode.
Sd06
External air temperature differential in Chiller
mode.
Sd07
External air temperature differential in Heat
Pump mode.
36.4
Energy Saving Parameters
ES01
Energy Saving start time
ES02
Energy Saving stop time
ES03
Monday….ES09 Sunday
0 = Not enabled; 1 = Enabled
ES10
Energy Saving increment in Chiller mode.
ES11
Energy Saving differential in Chiller mode.
ES12
Energy Saving increment in Heat Pump mode.
ES13
Energy Saving differential in Heat Pump mode.
36.5
Compressor Parameters
CO01
Minimum ON time after compressor activation.
CO02
Minimum OFF time after compressor de-
activation. During this time the corresponding icon is
blinking.
CO03
Delay time between compressor or stage
activation to reduce current peak consumption. During
this time the corresponding icon is blinking.
When working with a compressor with stage, if there
is a full load request, the stage solenoid is activated
and only after 5 seconds the compressor. After the
delay time CO03 if not needed the stage solenoid is
turned off.
CO04
Off delay time between compressor or stage
valve.
CO05
Delay time at power supply start-up.
All the output relays are delayed for the time set in
this parameter to prevent compressor damages from
frequent power supply black-outs.
CO06
Compressor switch on delay time after “water
pump / air supply fan” relay activation.
Having CO11 = 2 (“water pump / air supply fan”
related to compressor on/off status), the “water pump
/ air supply fan” always starts before the compressors.
Having CO11 = 1 (continuously running of pump/fan)
the relay switches on when the controller is turned on
in Chiller or Heat Pump mode. No delay time are
enabled.