IC100C Series
PRELIMINARY
1592015000 Manual IC100C Series 28/05/03 Page 27 di 38
37.
P
ARAMETER
T
ABLE
SUB MENU SELECTIONS
LABEL
Meaning
ALL
Shows the whole set of parameters
ST
It contains only the regulation parameters
CF
It contains only the configuration parameters
SD
It contains only the dynamic Set point parameters
ES
It contains only the Energy Saving parameters
CO
It contains only the compressor parameters
FA
It contains only the fan regulation parameters
Ar
It contains only the anti freeze parameters
DF
It contains only the defrost parameters
AL
It contains only the alarm parameters
LG
It contains only the logging parameters
PARAMETER DESCRIPTION
Regulation Parameters
Parameter
Description
Min
Max
Meas. Resolution
ST01
Summer Set point
ST05
ST06
°C/°F
Decimal
integer
ST02
Summer differential
0.0
0
25.0
45
°C
°F
Decimal
integer
ST03
Winter Set point
ST07
ST08
°C/°F
Decimal
integer
ST04
Winter differential
0.0
0
25.0
45
°C
°F
Decimal
integer
ST05
Minimum set point limit for ST01 (summer)
-40.0
-40.0
ST01
°C
°F
Decimal
integer
ST06
Maximum set point limit for ST01 (summer)
ST01
110
230
°C
°F
Decimal
integer
ST07
Minimum set point limit for ST03 (winter)
-40.0
-40.0
ST03
°C
°F
Decimal
integer
ST08
Maximum set point limit for ST03 (winter)
ST03
110
230
°C
°F
Decimal
integer
ST09
Regulation band
0.0
0
25.0
45
°C
°F
Decimal
integer
Pr2
Password 0
999