IC70CX
Pag. 8 of 23
The type of the probes can be selected by C05 parameter:
C05=PTC PTC probes are used
C05=NTC NTC probes are used
The unit of measure of the temperature can be:
C06=°C temperatures are showed in °C
C06=°F temperatures are showed in °F
For °C visualization it is possible to choose if the temperature has to be showed with decimal point or not:
C07=DE temperatures are showed with decimal point
C07=°F temperatures are showed without decimal point
10.1
Compressor
The compressor is used to maintain the set point temperature (S01 parameter).
It is possible to set a minimum OFF time (parameter C02) to avoid consecutive short cycles of the compressor.
If the regulation probe is faulty, the compressor will run with ON/OFF cycles defined by C03 and C04 parameters.
10.2
Heaters
Heaters can be used to integrate the compressor to produce hot water; to the compressor contribution is possible to add
electrical heaters contribution if the boiler temperature falls below a determined value set by parameter.