IC70CX
Pag. 17 of 23
F 04
Fan on time with compressor off
0÷15 (min.)
1°C / 1°F
F 05
Fan off time with compressor off
0÷15 (min.)
1°C / 1°F
A 01
Temperature alarms configuration
rE(0) - Ab(1)
-
A 02
Probe selection for temperature alarms
nP(0) - P1(1) - P2(2) -
P3(3) - P4(4)
-
A 03
Set point maximum temperature alarm
°C[0.0° ÷ 50.0° o ALL
÷ 150,0°]
°F[0° ÷ 90° o ALL ÷
0,1°C / 1°F
A 04
Set point minimum temperature alarm
°C[0.0° ÷ 50.0° o -
55.0° ÷ ALU]
°F[0° ÷ 90° o -67.0°
0,1°C / 1°F
A 05
Differential for temperature alarm
[0,1°C ÷ 25,5°C] [1°F
÷ 45°F]
A 06
Temperature alarm delay
0 ÷ 255 (min.)
1 minute
A 07
Compressor and heaters off in case of low temperature alarm
n(0) - Y(1)
A 08
Compressor and heaters off in case of high temperature alarm
n(0) - Y(1)
A 09
Temperature alarm detection delay at start up
0 ÷ 24H0(144)
10 minutes
A 10
Probe selection for temperature alarm 2
nP(0) - P1(1) - P2(2) -
P3(3) - P4(4)
A 11
Low temperature alarm 2 set point (absolute temperature)
[-55.0°C ÷ 150,0°C]
[-67°F ÷ 302°F]
A 12
High temperature alarm 2 set point (absolute temperature)
[-55.0°C ÷ 150,0°C]
[-67°F ÷ 302°F]
0,1°C / 1°F
A 13
Temperature alarm 2 differential
[0,1°C ÷ 25,5°C] [1°F
÷ 45°F]
A 14
Temperature alarm 2 delay
0 ÷ 254 (min.) ,
255=nU
1 minute
A 15
Temperature alarm delay at power-on
0 ÷ 24H0(144)
A 16
Compressor and heaters switched off in case of low temperature alarm 2
n(0) - Y(1)
A 17
Compressor and heaters switched off in case of high temperature alarm 2
n(0) - Y(1)
-
A 18
Alarm relay switched off by pushing a key
n(0) - Y(1)
-
A 19
Digital input 1 alarm delay
0 ÷ 255 (min.)
1 minute
A 20
Number of activation of pressure switch
0 ÷ 15
A 21
Alarm relay polarity
OP(0) - CL(1)
-