IC70CX
Pag. 15 of 23
13.
Parameters
rtC
Access to clock menu
Hur
Hour
Min
Minutes
dAy
Day of the week
S 01
Set point
S03
S04
0,1 °C / 1°F
S 02
Differential
0,1°C ÷ 25,5°C
1°F ÷ 45°F
0,1°C / 1°F
S 03
Minimum value of the set point
-55,0°C ÷ S01
-67°F ÷ S01
0,1°C / 1°F
S 04
Maximum value of the set point
S01 ÷ 150,0°C
S01 ÷ 302°F
0,1°C / 1°F
S 05
Set point heater for integration to compressor
-55,0°C ÷ 110°C
-67°F ÷ 230 °F
S 06
Differential heater for integration to compressor
0,1°C ÷ 25,5°C
1°F ÷ 45°F
S 07
heater activation delay
0 ÷ 255 (min.)
1 minute
S 08
Set point heater on evaporator probe
-55,0°C ÷ 110°C
-67°F ÷ 230 °F
S 09
Differential heater on evaporator probe
0,1°C ÷ 25,5°C
1°F ÷ 45°F
S 10
Set point to switch off compressor on evaporator probe
-55,0°C ÷ 110°C
-67°F ÷ 230 °F
S 11
Differential to switch on compressor on evaporator probe
0,1°C ÷ 25,5°C
1°F ÷ 45°F
S 12
Set point for anti legionella cycle
-55.0°C ÷ 150,0°C
-67°F ÷ 302°F
S 13
Time to reach anti legionella set point
0 ÷ 24H0(144)
10 minute
S 14
First defrost after start-up
n(0) - Y(1)
-
S 15
Antilegionella start time
0 ÷ 23h5 (143)
10 minutes
S 16
Antilegionella duration
0 ÷ 255 (min.)
1 minute
S 17
Day to activate anti legionella cycle
Sun(0) ÷ SAt(6) -
nu(7)
C 01
Delay to start regulation at start up
0 ÷ 255 (min.)
1 minute
C 02
Compressor anti-short cycle delay
0 ÷ 50 (min.)
1 minute
C 03
Compressor ON time if regulation faulty probe
0 ÷ 255 (min.)
1 minute
C 04
Compressor OFF time if regulation faulty probe
0 ÷ 255 (min.)
1 minute
C 05
Probe selection
PtC(0) - ntC(1)
C 06
Temperature unit of measure
°C(0) - °F(1)
-
C 07
Temperature visualization resolution
dE(0) - in(1)
-
C 08
Pb2 Evaporator probe presence
n(0) - Y(1)
-
C 09
Pb3 probe presence
n(0) - Y(1)
-
C 10
Pb4 probe presence
n(0) - Y(1)
-