19
49HZ. (Default: 47.0Hz)
For 60Hz output frequency models:
55-59Hz:
setting the frequency low loss point from 55Hz to
59Hz. (Default: 57.0Hz)
09: Programmable outlets enable/disable
Interface
Setting
Parameter 2:
Enable or disable programmable outlets.
ENA:
Programmable outlets enable
DIS:
Programmable outlets disable (Default)
10: Programmable outlets setting
Interface
Setting
Parameter 2:
Set up backup time limits for programmable
outlets.
0-999:
setting the backup time limits in minutes from 0-999
for programmable outlets which connect to non-critical
devices on battery mode. (Default: 999)
11: Autonomy limitation setting
Interface
Setting
Parameter 2:
Set up backup time on battery mode for
general outlets.
0-999:
setting the backup time in minutes from 0-999 for
general outlets on battery mode.
DIS:
Disable the autonomy limitation and the backup time
will depend on battery capacity. (Default)
Note:
When setting as “0”, the backup time will be only 10
seconds.
12: Battery total AH setting
Interface
Setting
Parameter 2:
Set up the battery total AH of the UPS.
7-999:
setting the battery total capacity from 7-999 in AH.
Please set the correct battery total capacity if external
battery bank is connected.