17
3-5. UPS Setting
Parameter 1
Parameter 2
There are three parameters to set up the UPS.
Parameter 1: It’s for program alternatives.
Refer to below table.
Parameter 2 is the setting options or values
for each program.
01: Output voltage setting
Interface
Setting
Parameter 2: Output voltage
For 100/110/115/120/125/127Vac models, you may choose
the following output voltage:
100:
presents output voltage is 100Vac
110:
presents output voltage is 110Vac
115:
presents output voltage is 115Vac
120:
presents output voltage is 120Vac (Default)
125:
presents output voltage is 125Vac
127:
presents output voltage is 127Vac
(127Vac is not applicable in USA region)
02: Frequency Converter enable/disable
Interface
Setting
Parameter 2:
Enable or disable converter mode. You may
choose the following two options:
CF ENA:
converter mode enable
CF DIS:
converter mode disable (Default)
03: Output frequency setting
Interface
Setting
Parameter 2: Output frequency setting.
You may set the initial frequency on battery mode:
BAT 50:
presents output frequency is 50Hz
BAT 60:
presents output frequency is 60Hz
If converter mode is enabled, you may choose the following
output frequency:
CF 50:
presents output frequency is 50Hz
CF 60:
presents output frequency is 60Hz
04: ECO enable/disable
Interface
Setting
Parameter 2:
Enable or disable ECO function. You may
choose the following two options:
ENA:
ECO mode enable
DIS:
ECO mode disable (Default)