10
Step 6: Disable and enable EPO function
This UPS is equipped with EPO function. By default, the UPS is delivered from factory with Pin
1 and pin 2 closed (a metal plate is connected to Pin 1 and Pin2) for UPS normal operation. To
activate EPO function, remove two screws on EPO port and metal plate will be removed.
Note:
The EPO function logic can be set up via LCD setting. Please refer to program 16 in UPS
setting for the details.
Step 7: Turn on the UPS
Press the ON/Mute button on the front panel for two seconds to power on the UPS.
Note: The battery charges fully during the first five hours of normal operation. Do not
expect full battery run capability during this initial charge period.
Step 8: Install software
For optimal computer system protection, install UPS monitoring software to fully configure UPS
shutdown. Use supplied RS-232 or USB communication cable to connect RS-232/USB port of
UPS and RS-232/USB port of PC. Then, follow below steps to install monitoring software.
1.
Insert the included installation CD into CD-ROM drive and then follow the on-screen
instructions to proceed software installation. If there no screen shows 1 minute after
inserting the CD, please execute setup.exe file for initiating software installation.
2.
Follow the on-screen instructions to install the software.
3.
When your computer restarts, the monitoring software will appear as an orange plug icon
located in the system tray, near the clock.
2-5. Battery Replacement
When the icons of
and
are flashing in LCD display and alarm is sounding every 2
seconds, it’s time to replace batteries. Contact your service representative to replace batteries.
Do not disconnect battery connectors under load If you prefer to remove input power to
change the batteries, press the OFF button on the front panel for two seconds to power off the
UPS and switch off utility power where the UPS is connected.
NOTE 1 :
DO NOT DISCONNECT the batteries while the UPS is in Battery mode.
NOTE 2 :
A small amount of arcing may occur when connecting the internal batteries. This is
normal condition and no harm for personnel. Connect the cables quickly and firmly.
NOTE 3 :
This UPS is equipped with internal batteries and only service person can replace the
batteries.
NOTE 4 :
Upon battery disconnection, equipment is not protected from power outages.
It’s in closed status for UPS
normal operation as default.
To activate EPO
function, remove
these two screws.