12
E1T - IP1897
GB
2.2 Dip-Switches
Description
OFF
ON
DIP1 Control 1-3 function.
Step-by-Step.
Opening.
DIP2 Restore automatic closing time.
50%
100%
DIP3 Preflashing set at 3 s.
Disabled during opening.
Enabled only with automatic closing with TC
>3 s.
Enabled for both opening and closing.
DIP4 Application type.
Sliding gate or sectional door.
DO NOT USE
DIP5 Dynamic brake.
Disabled.
DO NOT USE
DIP6 FUTURE USE
/
DO NOT USE
2.3 Bridges
Description
OFF
ON
SO Reversal safety switch function.
With the automation blocked, if the contacts
1-8 or 41-8 are open, it is possible to
activate the opening operation.
With the automation blocked, if the con-
tacts 1-8 or 41-8 are open, any operation
is impossible.
EO DO NOT USE
/
/
2.4 Signals
LED
ON
Flashing
POWER
24 V= power supply.
/
SA
Indicates that at least one of the safety contacts
is open.
- Indicates the STOP operation activated by push-
button panel PT4 (if present).
- If the SOFA1-SOFA2 device is installed, this
indicates a safety test failure (terminal 41).
- On power on, the LED flashes to indicate the
number of operations performed:
each rapid flash = 1000 operations
each slow flash = 10000 operations
IN
Activated at every command and adjustment to
the dip-switch and jumper.
/
11
Indicates that the 0-11 limit switch contact is open.
/
12
Indicates that the 0-12 limit switch contact is open.
/
17
FUTURE USE
3. STARTING
ATTENTION: The operations regarding point 3.3 are without safety devices.
3.1 Bridge the NC safety contacts with a jumper.
3.2 Set DIP4=OFF.
3.3 Switch on power.
Perform opening and closing commands and check that the automation functions correctly and that the limit switches are
correctly set.
Note: if the direction of rotation of the motor is incorrect for the desired direction of movement, swap the L2 and L3 phases.
3.4 Connect the safety devices (removing the relative jumpers) and check that they function correctly.
Note: ensure that the forces exerted by the door wings are compliant with EN12453-EN12445 regulations.
3.5 If required, activate automatic closing and adjust with the TC trimmer.
3.6 Set the partial opening with RP if required.
3.7 If required, connect the radio receiver to the relative OPEN connector, programme the transmitters as described in the relative
manual and check that all elements function correctly.
3.8 Connect any other accessories and check operation.
3.9 Once the start up and check procedures are completed, close the container.